| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, THE PLANS ARE NOT CLEAR AS TO WHICH |
| | AREAS ARE BEING RENOVATED. THE MAJORITY OF SYMBOL |
| | INDICATORS HAVE BEEN BLACKED OUT ON THE FOLLOWING PLAN |
| | SHEETS: SP101, SP102, A101, A102, A104, A105, A106, & |
| | A107. |
| | 2.) FBC R 301.2/FBC B 107.2.1, THE FOLLOWING PLAN SHEET |
| | NOTES NEED TO BE CORRECTED FROM FBC CODE 2001 TO FBC R |
| | 2020 AND THE WIND SPEED FROM 140MPH TO 170 VULT: S101 & |
| | S102. |
| | 3.) FBC B 107.3.4.1, THE COVER SHEET HAS AN AREA |
| | LABELED DEFERRED SUBMITTALS BUT THERE ARE NO DEFERRED |
| | SUBMITTALS LISTED. PLEASE INDICATE THE INTENDED |
| | DEFERRED SUBMITTALS OR REMOVE NOTE IF THERE ARE NO |
| | INTENDED DEFERRED SUBMITTALS. |
| | 4.) FBC R 905.3.3, PROVIDE UNDERLAYMENT DETAILS AND |
| | SUBMIT PRODUCT APPROVAL FOR CLAY TILE ROOFING |
| | UNDERLAYMENT. NOTE: A ROOFING SUB-PERMIT IS REQUIRED. |
| | 5.) FBC R301.2.1.2, PROVIDE DESIGN WIND LOAD PRESSURES |
| | AND REQUIREMENTS FOR WINDOW AND DOOR OPENINGS ON. THIS |
| | INFORMATION NEEDS TO BE ON PLAN SHEETS. THE PRODUCT |
| | APPROVALS ARE ALSO REQUIRED FOR ALL WINDOWS AND DOORS |
| | INCLUDING GARAGE DOOR. |
| | |
| | NOTE: PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS |
| | MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |