| Plan Review Notes For Permit 22051479 |
| Permit Number |
22051479 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-01 14:30:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. WHISPERMAT LVT IS PROPOSED. WE DO NOT HAVE ANY TEST | | | REPORTS ON FILE FOR THIS PRODUCT. THEREFORE PLEASE | | | SUBMIT THE FOLLOWING (SEE ALSO PREVIOUS COMMENT LIST): | | | | | | A, B. STC/IIC, PROVIDE TEST REPORTS. WE DO NOT ACCEPT | | | SPEC SHEETS, WE REQUIRE THE TEST REPORTS. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | |
|