2022-09-07 12:01:513RD REVIEW FBC-2020 RES. GAS
 PERMIT- 22051470
 9/7/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED
 ON REVISED PLAN SHEETS P-1 & P-2.
  
 1) THE RISER SHOWS AN EXISTING 18 FT. SECTION OF ?-INCH
 PE PIPE FROM THE METER TO THE FIRST TEE WHICH MUST BE
 INCREASED IN SIZE TO 1-INCH BASED ON TABLE 402.4(22)
 FBC FG. THE ?-INCH CAN SUPPLY A MAXIMUM 949,000 BTUS AT
 125FT. TOTAL DEVELOPED LENGTH. THE TOTAL LOAD OF SYSTEM
 SHOWN IN THE RISER IS 1,348,000 BTUS. PLEASE NOTE THE
 RISER APPROVED UNDER PREVIOUS PERMIT 17110370 SHOWS TWO
 TEES OFF THE MAIN SUPPLY PIPE AT THE METER- ONE TEE FOR
 THE UNDERGROUND PE, AND ONE FOR THE INTERIOR SCHEDULE
 40 METALLIC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  