| Plan Review Notes For Permit 22051470 |
| Permit Number |
22051470 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-07 12:01:51 | 3RD REVIEW FBC-2020 RES. GAS | | | PERMIT- 22051470 | | | 9/7/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED | | | ON REVISED PLAN SHEETS P-1 & P-2. | | | | | | 1) THE RISER SHOWS AN EXISTING 18 FT. SECTION OF ?-INCH | | | PE PIPE FROM THE METER TO THE FIRST TEE WHICH MUST BE | | | INCREASED IN SIZE TO 1-INCH BASED ON TABLE 402.4(22) | | | FBC FG. THE ?-INCH CAN SUPPLY A MAXIMUM 949,000 BTUS AT | | | 125FT. TOTAL DEVELOPED LENGTH. THE TOTAL LOAD OF SYSTEM | | | SHOWN IN THE RISER IS 1,348,000 BTUS. PLEASE NOTE THE | | | RISER APPROVED UNDER PREVIOUS PERMIT 17110370 SHOWS TWO | | | TEES OFF THE MAIN SUPPLY PIPE AT THE METER- ONE TEE FOR | | | THE UNDERGROUND PE, AND ONE FOR THE INTERIOR SCHEDULE | | | 40 METALLIC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB. | | | |
|