Plan Review Notes
Plan Review Notes For Permit 22051470
Permit Number 22051470
Review Stop G
Sequence Number 2
Notes
Date Text
2022-08-12 16:20:322ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22051470
 8/12/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED
 ON REVISED PLAN SHEETS P-1 & P-2.
  
 1) THE NEW RISER SPECIFYING SCHEDULE 40 METALLIC GAS
 PIPING THROUGHOUT THE ENTIRE SYSTEM, INCLUDING
 UNDERGROUND, DOES NOT MATCH THE PREVIOUS RISER DRAWING
 APPROVED UNDER PERMIT 17110370 FOR THE 48KW GENERATOR
 WHICH SHOWS PE UNDERGROUND OUTSIDE OF THE HOUSE AND
 CSST INSIDE THE RESIDENCE SUPPLYING THE DRYERS AND TWO
 OF THE TANKLESS WATER HEATERS- SEC. 107.2.1 WPB. PLEASE
 NOTE THAT STEEL PIPING MAY ONLY BE RUN UNDERGROUND IF
 PROPERLY PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SEC. G2415.11.2 FBC RES:
 G2415.11.2 PROTECTION METHODS.
 UNDERGROUND PIPING SHALL COMPLY WITH ONE OR MORE OF THE
 FOLLOWING:
 1.THE PIPING SHALL BE MADE OF CORROSION-RESISTANT
 MATERIAL THAT IS SUITABLE FOR THE ENVIRONMENT IN WHICH
 IT WILL BE INSTALLED.
 2.PIPE SHALL HAVE A FACTORY-APPLIED, ELECTRICALLY
 INSULATING COATING. FITTINGS AND JOINTS BETWEEN
 SECTIONS OF COATED PIPE SHALL BE COATED IN ACCORDANCE
 WITH THE COATING MANUFACTURER?S INSTRUCTIONS.
 3.THE PIPING SHALL HAVE A CATHODIC PROTECTION SYSTEM
 INSTALLED AND THE SYSTEM SHALL BE MONITORED AND
 MAINTAINED IN ACCORDANCE WITH AN APPROVED PROGRAM.
  
 REFER TO SECS. G2412.3 & G2412.4 FBC RES AND PROVIDE A
 COMPLETE GAS RISER AND PLAN FOR THE RESIDENCE THAT
 INCLUDES THE FOLLOWING INFORMATION:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING SUPPLYING THE EXISTING
 APPLIANCES AND THE NEW WATER HEATER.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS AND SHUTOFF VALVES.
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB.
  