| 2022-08-12 16:20:32 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22051470 |
| | 8/12/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW ARE BASED |
| | ON REVISED PLAN SHEETS P-1 & P-2. |
| | |
| | 1) THE NEW RISER SPECIFYING SCHEDULE 40 METALLIC GAS |
| | PIPING THROUGHOUT THE ENTIRE SYSTEM, INCLUDING |
| | UNDERGROUND, DOES NOT MATCH THE PREVIOUS RISER DRAWING |
| | APPROVED UNDER PERMIT 17110370 FOR THE 48KW GENERATOR |
| | WHICH SHOWS PE UNDERGROUND OUTSIDE OF THE HOUSE AND |
| | CSST INSIDE THE RESIDENCE SUPPLYING THE DRYERS AND TWO |
| | OF THE TANKLESS WATER HEATERS- SEC. 107.2.1 WPB. PLEASE |
| | NOTE THAT STEEL PIPING MAY ONLY BE RUN UNDERGROUND IF |
| | PROPERLY PROTECTED FROM CORROSION IN ACCORDANCE WITH |
| | SEC. G2415.11.2 FBC RES: |
| | G2415.11.2 PROTECTION METHODS. |
| | UNDERGROUND PIPING SHALL COMPLY WITH ONE OR MORE OF THE |
| | FOLLOWING: |
| | 1.THE PIPING SHALL BE MADE OF CORROSION-RESISTANT |
| | MATERIAL THAT IS SUITABLE FOR THE ENVIRONMENT IN WHICH |
| | IT WILL BE INSTALLED. |
| | 2.PIPE SHALL HAVE A FACTORY-APPLIED, ELECTRICALLY |
| | INSULATING COATING. FITTINGS AND JOINTS BETWEEN |
| | SECTIONS OF COATED PIPE SHALL BE COATED IN ACCORDANCE |
| | WITH THE COATING MANUFACTURER?S INSTRUCTIONS. |
| | 3.THE PIPING SHALL HAVE A CATHODIC PROTECTION SYSTEM |
| | INSTALLED AND THE SYSTEM SHALL BE MONITORED AND |
| | MAINTAINED IN ACCORDANCE WITH AN APPROVED PROGRAM. |
| | |
| | REFER TO SECS. G2412.3 & G2412.4 FBC RES AND PROVIDE A |
| | COMPLETE GAS RISER AND PLAN FOR THE RESIDENCE THAT |
| | INCLUDES THE FOLLOWING INFORMATION: |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | C) TYPES AND SIZES OF PIPING SUPPLYING THE EXISTING |
| | APPLIANCES AND THE NEW WATER HEATER. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) LOCATIONS OF REGULATORS AND SHUTOFF VALVES. |
| | G) OUTLET PRESSURES AT REGULATORS. |
| | H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | I) PIPE SIZING TABLES |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |