Plan Review Notes
Plan Review Notes For Permit 22051470
Permit Number 22051470
Review Stop G
Sequence Number 1
Notes
Date Text
2022-06-22 07:43:511ST REVIEW FBC-2020 RES. GAS
  
 PERMIT- 22051470
  
 6/22/22
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
  
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
  
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
  
 FS- FLORIDA STATUTES
  
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1, P-2: PROVIDE A GAS RISER DRAWING FOR THE
 RELOCATED TANKLESS WATER HEATER- SEC. 107.3.5.3 WPB.
  
 2) P-1: THE RELOCATED GAS WATER HEATER APPEARS TO BE
 WITHIN THE REQUIRED 4 FT. HORIZONTAL CLEARANCE TO THE
 WINDOW. PLEASE PROVIDE CLEARANCE DISTANCE MEASUREMENTS
 ON THE PLAN TO COMPLY WITH SECS. G2427.8 & G2448.1 FBC
 RES.
  
 3) P-1: PROVIDE A NOTE ON PLACE A NOTE INDICATE
 CONDENSATE FROM THE WATER HEATER WILL BE NEUTRALIZED
 PER THE MANUFACTURER'S SPECIFICATIONS AND CONVEY TO A
 DISPOSAL LOCATION A MINIMUM OF 12-INCHES FROM THE
 BUILDING- SEC. 307.2 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
  
 MECHANICAL/PLUMBING PLANS EXAMINER
  
 401 CLEMATIS STREET
  
 WEST PALM BEACH FL 33401
  
 561-805-6719
  
 [email protected]
  