| Plan Review Notes For Permit 22051470 |
| Permit Number |
22051470 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-22 07:43:51 | 1ST REVIEW FBC-2020 RES. GAS | | | | | | PERMIT- 22051470 | | | | | | 6/22/22 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | | | | FS- FLORIDA STATUTES | | | | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-1, P-2: PROVIDE A GAS RISER DRAWING FOR THE | | | RELOCATED TANKLESS WATER HEATER- SEC. 107.3.5.3 WPB. | | | | | | 2) P-1: THE RELOCATED GAS WATER HEATER APPEARS TO BE | | | WITHIN THE REQUIRED 4 FT. HORIZONTAL CLEARANCE TO THE | | | WINDOW. PLEASE PROVIDE CLEARANCE DISTANCE MEASUREMENTS | | | ON THE PLAN TO COMPLY WITH SECS. G2427.8 & G2448.1 FBC | | | RES. | | | | | | 3) P-1: PROVIDE A NOTE ON PLACE A NOTE INDICATE | | | CONDENSATE FROM THE WATER HEATER WILL BE NEUTRALIZED | | | PER THE MANUFACTURER'S SPECIFICATIONS AND CONVEY TO A | | | DISPOSAL LOCATION A MINIMUM OF 12-INCHES FROM THE | | | BUILDING- SEC. 307.2 FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | | | | 401 CLEMATIS STREET | | | | | | WEST PALM BEACH FL 33401 | | | | | | 561-805-6719 | | | | | | [email protected] | | | |
|