| Date |
Text |
| 2022-07-12 09:48:06 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR DOOR, WINDOWS, |
| | ROOFING SYSTEM. |
| | |
| | 2) PLEASE SHOW THE BUILDING USE PER FBC CHAPTER 3 |
| | |
| | 3) PLEASE PROVIDE ALL FRAMING DETAILS - EXTERIOR WALLS, |
| | FLOOR, ROOF. |
| | |
| | 4) PLEASE SHOW THE EXTERIOR WALL CLADDING DETAILS - |
| | PLEASE SHOW ALL ATTACHMENT (TYPE, SIZE ON CENTER |
| | SPACING ETC.) FBC 1403 |
| | |
| | 5) PLEASE PROVIDE STAIR DETAILS FBC 107 |
| | |
| | 6) PLEASE SHOW STAIR HAND RAIL DETAILS - ATTACHMENTS, |
| | HEIGHT ETC FBC 1014 |
| | |
| | 7) PLEASE SHOW STAIR GUARD RAIL DETAILS - ATTACHMENTS, |
| | HEIGHT ETC. FBC 1015 |
| | |
| | 8) PLEASE SHOW THE EXTERIOR DOOR LANDING - FBC 1010.1.5 |
| | FLOOR ELEVATION. |
| | THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF A |
| | DOOR. SUCH FLOOR OR LANDING SHALL BE AT THE SAME |
| | ELEVATION ON EACH SIDE OF THE DOOR. LANDINGS SHALL BE |
| | LEVEL EXCEPT FOR EXTERIOR LANDINGS, WHICH ARE PERMITTED |
| | TO HAVE A SLOPE NOT TO EXCEED 0.25 UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE). |
| | |
| | 9) PLEASE SHOW THE DOOR LANDING SIZE FBC 1010.1.6 |
| | LANDINGS AT DOORS. |
| | LANDINGS SHALL HAVE A WIDTH NOT LESS THAN THE WIDTH OF |
| | THE STAIRWAY OR THE DOOR, WHICHEVER IS GREATER. DOORS |
| | IN THE FULLY OPEN POSITION SHALL NOT REDUCE A REQUIRED |
| | DIMENSION BY MORE THAN 7 INCHES (178 MM). WHERE A |
| | LANDING SERVES AN OCCUPANT LOAD OF 50 OR MORE, DOORS IN |
| | ANY POSITION SHALL NOT REDUCE THE LANDING TO LESS THAN |
| | ONE-HALF ITS REQUIRED WIDTH. LANDINGS SHALL HAVE A |
| | LENGTH MEASURED IN THE DIRECTION OF TRAVEL OF NOT LESS |
| | THAN 44 INCHES (1118 MM). |
| | |
| | 10) PLEASE SHOW ON THE LOCATION OF THE BLDG ON THE SITE |
| | PLAN (SHOW SETBACKS FROM THE PROPERTY LINES). FBC WPB |
| | 107.2.5 |
| | |
| | 11) PLEASE SHOW THE WIND DESIGN DATA ON THE DRAWINGS - |
| | FBC 1603.1.4 |
| | |
| | 12) PLEASE SHOW THE LOWEST FLOOR ELEVATION - THE |
| | PROPERTY IS IN A FLOOD ZONE (AE 6 OR AE7) DEPENDING ON |
| | THE LOCATION OF THE BLDG. LOWEST FLOOR ELEVATION WILL |
| | NEED TO BE 2 FEET ABOVE THE FEMA BASE FLOOD ELEVATION - |
| | CITY ORD: NO. 4729-17 SECTION 5 SEC. 18-3 (B) 1612.4. |