| 2022-08-29 14:43:36 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22051468 |
| | 8/29//2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | BASED ON THE NARRATIVE RESPONSE TO COMMENTS IT APPEARS |
| | THAT SOME OF THE CORRECTED PLANS WERE NOT UPLOADED. |
| | |
| | 1) FAILED. A-1.0: PROVIDE THE CLEAR FLOOR SPACE |
| | DIMENSIONS FOR THE ACCESSIBLE WATER CLOSET AND LAVATORY |
| | SINK- SECS. 604.3 & 606.2 FBC ACCO |
| | REQUESTED CLEAR FLOOR SPACE DIMENSIONS NOT PROVIDED |
| | |
| | 2) FAILED. A-7.0: SHOW THE HEIGHT OF THE WATER CLOSET |
| | MEASURED FROM THE FINISHED FLOOR TO THE TOP OF THE |
| | SEAT- SEC. 604.4 FBC ACC. |
| | NOT PROVIDED. THE DETAIL 4 SHOWS THE HEIGHT DIMENSION |
| | MESURED TO THE RIM OF THE WATER CLOSET AND NOT THE SEAT |
| | AS REQUIRED. |
| | |
| | 3) FAILED. A-7.0: SHOW THE HEIGHT OF THE GRAB BARS |
| | MEASURED FROM THE FINISHED FLOORS TO THE TOPS OF THE |
| | GRIPPING SURFACES- SEC. 609.4 FBC ACC. |
| | NOT PROVIDED. THE DETAIL 4 SHOWS THE HEIGHT DIMENSION |
| | MEASURED TO THE CENTER OF THE GRAB BARS AND NOT THE |
| | TOPS AS REQUIRED. |
| | |
| | |
| | 4) FAILED. A-7.0: SHOW THE LOCATION OF THE TOILET PAPER |
| | DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSET |
| | TO THE CENTERLINE OF THE DISPENSER- SEC. 604.7 FBC ACC. |
| | THE DETAIL 4 SHOWS THE DIMENSION TO THE SIDE EDGE OF |
| | THE DISPENSER AND NOT THE CENTER AS REQUIRED. |
| | |
| | 5) FAILED. P-1.0: THE DISCHARGES FROM THE HAND SINK, |
| | ICE MAKER, AND ICE BIN SHALL NOT DRAIN INTO THE GREASE |
| | INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | THE CORRECTIONS WERE NOT MADE TO THE PLAN. |
| | |
| | 7) FAILED. P1.0: PROVIDE CLEANOUTS AT THE JUNCTIONS OF |
| | THE 2 AND 3-INCH SANITARY BUILDING DRAINS AND THE |
| | 4-INCH SEWER LINE- SEC. 708.1.3 FBC P. |
| | THE CORRECTIONS WERE NOT MADE TO THE PLAN. |
| | 10) FAILED. P-2.0 THE 1-INCH HOT WATER SUPPLY LINE TO |
| | THE LAVATORY IS EXCEEDING THE MAXIMUM .5 FT. DISTANCE |
| | FROM THE HOT WATER SOURCE- TABLE C404.5.1 FBC EC. |
| | THE CORRECTION WAS NOT MADE TO THE PLAN. |
| | |
| | 14) FAILED. A- 4: PROVIDE ROOF DRAINAGE PLANS AND |
| | CALCULATIONS- SECS. 1101.2, 1101.7, 1105.1, 1106.1, & |
| | 1108.1 FBC P. |
| | CALCULATIONS BASED ON RAINFALL RATE NOT PROVIDED. AREA |
| | AND GPM FLOW CALCULATIONS NOT PROVIDED. |
| | A) PROVIDE DOWNSPOUT SIZES. NOT PROVIDED |
| | C) PROVIDE AN OVERFLOW SCUPPER DETAIL. NOT PROVIDED. |
| | D) SHOW THE DRAINAGE FROM THE DOWNSPOUTS WILL DISCHARGE |
| | A MINIMUM OF 12-INCHES FROM THE BUILDING AND WILL BE |
| | CONVEYED TO AN APPROVED PLACE OF DISPOSAL. |
| | |
| | 15) P-5.0: CORRECT THE 3-COMPARTMENT SINK DETAIL TO |
| | SHOW EACH WELL OF THE FIXTURE DRAINING INDIVIDUALLY |
| | INTO THE FLOOR SINK- SEC. 802.1.1 FBC P |
| | |
| | THE DETAIL SHOWS ONE OF THE THREE DRAINS DISCHARGING TO |
| | THE FLOOR SINK AND NOT TO THE GREASE INTERCEPTOR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |