Plan Review Notes
Plan Review Notes For Permit 22051468
Permit Number 22051468
Review Stop M
Sequence Number 2
Notes
Date Text
2022-08-29 06:07:17PLEASE ADDRESS 1ST CYCLE COMMENTS BELOW. THE RESPONSE
 LETTER SUBMITTED THIS CYCLE INDICATED CORRECTIONS WERE
 MADE BUT THEY WERE NOT SUBMITTED.
  
 1ST REVIEW FMC
 PERMIT: 22051468
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC C402
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 3) ADD A NOTE ON THE MECHANICAL DRAWING STATING THE
 REFRIGERATION WILL NEED A SEPARATE PERMIT AND REVIEW AS
 IT WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 4) ADD A NOTE TO THE MECHANICAL DRAWING STATING THE
 HOODS SYSTEMS WILL NEED A SEPARATE PERMIT AND REVIEW AS
 IT WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 5) PROVIDE GUARD PROTECTION FOR EQUIPMENT ON THE ROOF.
 FMC 304.11
  
 6) PROVIDE THE OCCUPANCY CLASSIFICATION FOR THE OUTDOOR
 AIR CALCULATIONS BASE ON USE OF SPACE FROM FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
 7) PROVIDE SPECS. FOR THE COOKING EQUIPMENT. FMC 507.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  