2022-08-30 11:56:19NEW COMMERCIAL BLDG
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT
 DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE
 USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL.
  
 2) DRAWING A-7.0 - DETAIL 4 - THE TOILET PAPER
 DISPENSER DIMENSIONS FROM THE FACE OF THE TOILET SHOULD
 BE SHOWN TO THE CENTER OF THE TOILET PAPER DISPENSER.
 FBC A 604.7
  
 3) DRAWING A-7.0 - DETAIL 4 - GRAB BAR DIMENSIONS FROM
 THE FLOOR NEED TO BE SHOWN TO THE TOP OF THE GRAB BAR
 GRIPPING SURFACE - NOT THE CENTER. FBC 609.4
  
  
  
  
  