| 2022-08-30 11:56:19 | NEW COMMERCIAL BLDG | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE ROOF FLAT | | | DECK - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN | | | THE ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL. | | | | | | 2) DRAWING A-7.0 - DETAIL 4 - THE TOILET PAPER | | | DISPENSER DIMENSIONS FROM THE FACE OF THE TOILET SHOULD | | | BE SHOWN TO THE CENTER OF THE TOILET PAPER DISPENSER. | | | FBC A 604.7 | | | | | | 3) DRAWING A-7.0 - DETAIL 4 - GRAB BAR DIMENSIONS FROM | | | THE FLOOR NEED TO BE SHOWN TO THE TOP OF THE GRAB BAR | | | GRIPPING SURFACE - NOT THE CENTER. FBC 609.4 | | | | | | | | | | | | | | | |
|