| 2022-06-28 17:30:51 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22051468 |
| | 6/28/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A-1.0: PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS FOR |
| | THE ACCESSIBLE WATER CLOSET AND LAVATORY SINK- SECS. |
| | 604.3 & 606.2 FBC ACC. |
| | |
| | 2) A-7.0: SHOW THE HEIGHT OF THE WATER CLOSET MEASURED |
| | FROM THE FINISHED FLOOR TO THE TOP OF THE SEAT- SEC. |
| | 604.4 FBC ACC. |
| | |
| | 3) A-7.0: SHOW THE HEIGHT OF THE GRAB BARS MEASURED |
| | FROM THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING |
| | SURFACES- SEC. 609.4 FBC ACC. |
| | |
| | 4) A-7.0: SHOW THE LOCATION OF THE TOILET PAPER |
| | DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSET |
| | TO THE CENTERLINE OF THE DISPENSER- SEC. 604.7 FBC ACC. |
| | |
| | 5) P-1.0: THE DISCHARGES FROM THE HAND SINK, ICE MAKER, |
| | AND ICE BIN SHALL NOT DRAIN INTO THE GREASE |
| | INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | |
| | 6) P-1.0 & P2.0: SEPARATE PERMITS ARE REQUIRED FOR |
| | INSTALLATION OF THE GREASE INTERCEPTOR AND WATER |
| | SERVICE BACKFLOW PREVENTER- SECS. 105.1 & 107.2.1 WPB. |
| | |
| | DUE TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR AND |
| | BACKFLOW PREVENTER PERMITS ARE REQUIRED TO BE SUBMITTED |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT |
| | AN APPLICATION ?TBD? (TO BE DETERMINED) IF YOU DO NOT |
| | HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| | PERMIT APPLICATION TO [email protected] . YOU |
| | WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. |
| | YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT |
| | THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND |
| | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 7) P1.0: PROVIDE CLEANOUTS AT THE JUNCTIONS OF THE 2 |
| | AND 3-INCH SANITARY BUILDING DRAINS AND THE 4-INCH |
| | SEWER LINE- SEC. 708.1.3 FBC P. |
| | |
| | 8) P-2.0: PROVIDE A MEANS OF LIMITING THE HOT WATER |
| | DELIVERY TEMPERATURE AT THE FIXTURES AND EQUIPMENT |
| | OTHER THAN THE WATER HEATER THERMOSTAT- SEC. 607.1.1 |
| | FBC P. PROVIDE EITHER A MASTER THERMOSTATIC MIXING |
| | VALVE OR POINT OF USE MIXING VALVES. |
| | |
| | 9) P-2.0: INDICATE HOW TEMPERED WATER WILL BE DELIVERED |
| | FROM THE LAVATORY- SEC. 419.4 & 607.1.2 FBC P. |
| | |
| | 10) P-2.0 THE 1-INCH HOT WATER SUPPLY LINE TO THE |
| | LAVATORY IS EXCEEDING THE MAXIMUM .5 FT. DISTANCE FROM |
| | THE HOT WATER SOURCE- TABLE C404.5.1 FBC EC. |
| | |
| | 11) P-2.0: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS |
| | FOR SUPPLY LINES TO FIXTURES AND EQUIPMENT WITH QUICK |
| | CLOSING VALVES- SECS. 604.9 FBC P. |
| | |
| | 12) P-2.0 & P3.0: SHOW THE LOCATIONS OF BACKFLOW |
| | PREVENTERS FOR FILTERED WATER SUPPLY LINES TO THE |
| | COFFEE BREWERS, ESPRESSO MACHINE, SODA MACHINE, ICE |
| | MACHINE, ICE BIN, PROOFING CABINET, OVEN ETC.- SEC. |
| | 608.3 FBC P. PLEASE INCLUDE A DEVICE SCHEDULE |
| | INDICATING THE MAKES, MODELS AND TYPES OF BACKFLOW |
| | PREVENTERSTO BE IINSTALLED. |
| | |
| | 13) P2.0 P3.0: INDICATE HOW THE FILTRATION SYSTEM WILL |
| | PROTECTED FROM CONTAMINATION- SEC. 608.4 FBC P. |
| | |
| | 14) A- 4: PROVIDE ROOF DRAINAGE PLANS AND CALCULATIONS- |
| | SECS. 1101.2, 1101.7, 1105.1, 1106.1, & 1108.1 FBC P. |
| | A) PROVIDE DOWNSPOUT SIZES. |
| | B) PROVIDE THE WIDTH DIMENSION OF THE SCUPPER ON DETAIL |
| | 3. |
| | C) PROVIDE AN OVERFLOW SCUPPER DETAIL. |
| | D) SHOW THE DRAINAGE FROM THE DOWNSPOUTS WILL DISCHARGE |
| | A MINIMUM OF 12-INCHES FROM THE BUILDING AND WILL BE |
| | CONVEYED TO AN APPROVED PLACE OF DISPOSAL. |
| | |
| | 14) P-5.0: CORRECT THE 3-COMPARTMENT SINK DETAIL TO |
| | SHOW EACH WELL OF THE FIXTURE DRAINING INDIVIDUALLY |
| | INTO THE FLOOR SINK- SEC. 802.1.1 FBC P |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |