| 2022-06-30 13:48:23 | 1ST REVIEW FMC |
| | PERMIT: 22051468 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE ENERGY CALCULATIONS. FEC C402 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 3) ADD A NOTE ON THE MECHANICAL DRAWING STATING THE |
| | REFRIGERATION WILL NEED A SEPARATE PERMIT AND REVIEW AS |
| | IT WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 4) ADD A NOTE TO THE MECHANICAL DRAWING STATING THE |
| | HOODS SYSTEMS WILL NEED A SEPARATE PERMIT AND REVIEW AS |
| | IT WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 5) PROVIDE GUARD PROTECTION FOR EQUIPMENT ON THE ROOF. |
| | FMC 304.11 |
| | |
| | 6) PROVIDE THE OCCUPANCY CLASSIFICATION FOR THE OUTDOOR |
| | AIR CALCULATIONS BASE ON USE OF SPACE FROM FMC |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 7) PROVIDE SPECS. FOR THE COOKING EQUIPMENT. FMC 507.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |