2022-06-14 12:18:14FIRE COMMENTS:
  
 PROVIDE DETAIL ON DOOR LOCKING HARDWARE FROM THE SIDE
 OF EGRESS FOR ALL INTERIOR AND EXTERIOR DOORS. NFPA
 101, 7.2.1.5
  
 PROVIDE DOOR WIDTH (DOOR OPENING CLEAR WIDTH) FOR
 WALK-IN FREEZER AND DRY STORAGE ROOM DOORS. NFPA
 7.2.1.2.3
  
 PROVIDE EXIT SIGNS AND EMERGENCY LIGHTS FOR THE WALK-IN
 FREEZER AND DRY STORAGE ROOM. NFPA 101 7.9 & 7.10
  
 PROVIDE LISTING INFORMATION/ TEST DATA FOR THE TORNADO
 OVEN FOR VENTLESS APPLICATIONS. NFPA 96 12.1
  