| Plan Review Notes For Permit 22051468 |
| Permit Number |
22051468 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-14 12:18:14 | FIRE COMMENTS: | | | | | | PROVIDE DETAIL ON DOOR LOCKING HARDWARE FROM THE SIDE | | | OF EGRESS FOR ALL INTERIOR AND EXTERIOR DOORS. NFPA | | | 101, 7.2.1.5 | | | | | | PROVIDE DOOR WIDTH (DOOR OPENING CLEAR WIDTH) FOR | | | WALK-IN FREEZER AND DRY STORAGE ROOM DOORS. NFPA | | | 7.2.1.2.3 | | | | | | PROVIDE EXIT SIGNS AND EMERGENCY LIGHTS FOR THE WALK-IN | | | FREEZER AND DRY STORAGE ROOM. NFPA 101 7.9 & 7.10 | | | | | | PROVIDE LISTING INFORMATION/ TEST DATA FOR THE TORNADO | | | OVEN FOR VENTLESS APPLICATIONS. NFPA 96 12.1 | | | | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | | | | |
|