| Date |
Text |
| 2022-07-06 13:31:56 | NEW COMMERCIAL BLDG |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD. FBC WPB 107.3.4 |
| | |
| | 2) PLEASE PROVIDE A SOIL (GEOTECHNICAL) REPORT FBC |
| | 1803.1 |
| | |
| | 3) PLEASE SHOW THE SITE DRAINAGE ON THE SITE PLAN OR |
| | PROVIDE A STORM WATER DRAINAGE PLAN FBC WPB 107.2.5 |
| | |
| | 4) PLEASE PROVIDE A SURVEY. |
| | |
| | 5) DRAWING A-7.0 - DETAIL 4 - THE TOILET PAPER |
| | DISPENSER DIMENSIONS FROM THE FACE OF THE TOILET SHOULD |
| | BE SHOWN TO THE CENTER OF THE TOILET PAPER DISPENSER. |
| | FBC A 604.7 |
| | |
| | 6) DRAWING A-7.0 - DETAIL 4 - GRAB BAR DIMENSIONS FROM |
| | THE FLOOR NEED TO BE SHOWN TO THE TOP OF THE GRAB BAR |
| | GRIPPING SURFACE - NOT THE CENTER. FBC 609.4 |
| | |
| | 7) A SEPARATE PERMIT IS REQUIRED FOR SIGNS, PARKING |
| | LOT, DUMPSTER. |
| | |
| | 8) CANOPIES, ROOFING SYSTEMS, WINDOW AND DOOR PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |