2022-07-06 13:31:56NEW COMMERCIAL BLDG
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD. FBC WPB 107.3.4
  
 2) PLEASE PROVIDE A SOIL (GEOTECHNICAL) REPORT FBC
 1803.1
  
 3) PLEASE SHOW THE SITE DRAINAGE ON THE SITE PLAN OR
 PROVIDE A STORM WATER DRAINAGE PLAN FBC WPB 107.2.5
  
 4) PLEASE PROVIDE A SURVEY.
  
 5) DRAWING A-7.0 - DETAIL 4 - THE TOILET PAPER
 DISPENSER DIMENSIONS FROM THE FACE OF THE TOILET SHOULD
 BE SHOWN TO THE CENTER OF THE TOILET PAPER DISPENSER.
 FBC A 604.7
  
 6) DRAWING A-7.0 - DETAIL 4 - GRAB BAR DIMENSIONS FROM
 THE FLOOR NEED TO BE SHOWN TO THE TOP OF THE GRAB BAR
 GRIPPING SURFACE - NOT THE CENTER. FBC 609.4
  
 7) A SEPARATE PERMIT IS REQUIRED FOR SIGNS, PARKING
 LOT, DUMPSTER.
  
 8) CANOPIES, ROOFING SYSTEMS, WINDOW AND DOOR PRODUCT
 APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS
 TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  