Plan Review Notes
Plan Review Notes For Permit 22051463
Permit Number 22051463
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-03 14:30:34FIRE PROVISO:
 DEMO OF THE WING WALL MAY AFFECT FIRE SPRINKLER HEAD
 COVERAGE.
  
 A REVIEW BY A FIRE SPRINKLER CONTRACTOR MAY BE
 REQUIRED.
  
 SHOULD NO WORK BE REQUIRED, A LETTER FROM THAT
 CONTRACTOR WILL BE
 REQUIRED TO BE SUBMITTED ON FINAL FIRE INSPECTIONS TO
 THE FIRE INSPECTOR.
  
 SHOULD MODIFICATION BE REQUIRED IT SHALL BE UNDER
 SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  