| 2022-05-31 14:10:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF A NEW CLOSET AND NEW DROP |
| | CEILING AREAS. |
| | |
| | THESE NEW AREAS MAY AFFECT THE EXISTING FIRE SPRINKLER |
| | PROTECTION AND REQUIRE MODIFICATIONS PER NFPA 13. |
| | |
| | A FIRE SPRINKLER CONTRACTOR IS REQUIRED TO REVIEW THE |
| | PROPOSED WORK TO ENSURE CODE COMPLIANT COVERAGE IS |
| | MAINTAINED. |
| | |
| | SHOULD NO WORK BE REQUIRED, A LETTER FROM THAT |
| | CONTRACTOR WILL BE REQUIRED TO BE SUBMITTED ON FINAL |
| | FIRE INSPECTIONS TO THE FIRE INSPECTOR. |
| | |
| | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | 1A) THERE IS NO DETAIL REGARDING THE PROPOSED DROP |
| | CEILINGS, I.E. HEIGHT/WIDTH, NUMBER OF LIGHTS, TYPE OF |
| | LIGHTS, ETC. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | 2) THERE IS AN INDICATION OF NEW FLOORING ON THE |
| | SUBMITTED PLAN; HOWEVER THERE IS NO INDICTION OF WHERE |
| | THE NEW FLOOR IS LOCATED NOR THE TYPE OF FLOORING |
| | MATERIAL. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN |
| | INDICATING THE LOCATION AREAS OF THE PROPOSED FLOORING. |
| | |
| | |
| | |
| | 2A) PLEASE PROVIDE THE FLOORING TYPE I.E. CERAMIC, |
| | MARBLE, TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A |
| | SPEC SHEET. |
| | |
| | FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL |
| | PLANKS, CORK, WOOD PLEASE PROVIDE THE MANUFACTURE |
| | PRODUCT FLAME SPREAD/PRODUCT SAFETY TEST SHEET |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |