Plan Review Notes
Plan Review Notes For Permit 22051431
Permit Number 22051431
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-31 14:10:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A NEW CLOSET AND NEW DROP
 CEILING AREAS.
  
 THESE NEW AREAS MAY AFFECT THE EXISTING FIRE SPRINKLER
 PROTECTION AND REQUIRE MODIFICATIONS PER NFPA 13.
  
 A FIRE SPRINKLER CONTRACTOR IS REQUIRED TO REVIEW THE
 PROPOSED WORK TO ENSURE CODE COMPLIANT COVERAGE IS
 MAINTAINED.
  
 SHOULD NO WORK BE REQUIRED, A LETTER FROM THAT
 CONTRACTOR WILL BE REQUIRED TO BE SUBMITTED ON FINAL
 FIRE INSPECTIONS TO THE FIRE INSPECTOR.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
 1A) THERE IS NO DETAIL REGARDING THE PROPOSED DROP
 CEILINGS, I.E. HEIGHT/WIDTH, NUMBER OF LIGHTS, TYPE OF
 LIGHTS, ETC.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
 2) THERE IS AN INDICATION OF NEW FLOORING ON THE
 SUBMITTED PLAN; HOWEVER THERE IS NO INDICTION OF WHERE
 THE NEW FLOOR IS LOCATED NOR THE TYPE OF FLOORING
 MATERIAL.
  
 PER NFPA 1
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION AREAS OF THE PROPOSED FLOORING.
  
  
  
 2A) PLEASE PROVIDE THE FLOORING TYPE I.E. CERAMIC,
 MARBLE, TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A
 SPEC SHEET.
  
 FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL OR VINYL
 PLANKS, CORK, WOOD PLEASE PROVIDE THE MANUFACTURE
 PRODUCT FLAME SPREAD/PRODUCT SAFETY TEST SHEET
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  