| 2022-06-08 12:27:13 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22051368 |
| | 6/7/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED APPLICATION, CONTRACT, DOH RECEIPTS OF |
| | APPLICATION, AND PERMIT VALUE INDICATE NEW POOL AND SPA |
| | CONSTRUCTION HOWEVER ONLY THE SPA PLANS HAVE BEEN |
| | UPLOADED. PLEASE NOTE POOL AND SPA PERMITS ARE |
| | TYPICALLY ISSUED SEPARATELY. THE FOLLOWING REVIEW |
| | COMMENTS PERTAIN TO THE SPA ONLY- SECS. 105.1, 107.2.1 |
| | & 107.3.5.1.3 WPB. |
| | |
| | 2) SHEET 1: BECAUSE THE POOL RESTROOMS ARE BEING USED |
| | BY BOTH THE OCCUPANTS OF THE SPA AND POOL, PLEASE |
| | INDICATE THE SQUARE FOOTAGE OF THE POOL, AND THE SQUARE |
| | FOOTAGE OF THE DECK AREA ON THE PLAN- TABLE 454.1.6.1 & |
| | SECS. 454.1.6.1.1, 454.1.8.1 FBC B. |
| | |
| | 3) SHEETS 1: SHOW THE LOCATION OF THE REQUIRED HOSE |
| | BIBS WITH VACUUM BREAKERS EITHER IN, OR WITHIN 25 FT. |
| | OF THE MEN?S AND WOMEN?S POOL BATHROOMS- SEC. |
| | 454.1.6.1.4 FBC B. |
| | |
| | 4) SHEET 4: THE ISOMETRIC DRAWING SHOWS WASTEWATER FROM |
| | THE CARTRIDGE FILTER TO BE DRAINED INTO THE SANITARY |
| | SEWER WHICH IS PROHIBITED PER SEC. 90-126(5) WPB CODE |
| | OF ORDINANCES. PLEASE REVIEW THE FOLLOWING INFORMATION |
| | AND ADDRESS THE ISSUE. |
| | |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S |
| | SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | ? THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | ? NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | ? WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | ? DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | ? FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT |
| | O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR |
| | 561-822-2168. |
| | ? FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |