Plan Review Notes
Plan Review Notes For Permit 22051361
Permit Number 22051361
Review Stop B
Sequence Number 2
Notes
Date Text
2022-08-29 10:31:59NEW OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXTERIOR WALL STUD TO FLOOR JOIST
 CONNECTION - THERE SHOULD BE A STRAP OR HURRICANE
 ANCHOR AT THE BOTTOM OF THE WALL STUD - FBC 1604.8.1
 GENERAL.
 ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF
 WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO
 RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM
 THE APPLICATION OF THE PRESCRIBED LOADS.
  
 2) PRODUCT APPROVALS PROVIDED FOR THE GLAZED COMPONENTS
 (GLAZING IN DOORS AND WINDOWS) NEED TO MEET IMPACT
 REQUIREMENTS - OR PROVIDE SHUTTER PRODUCT APPROVALS -
 FBC 1609.1.2
  
 3) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE
 PRODUCT APPROVALS.
  
 4) ROOF SHEATHING ATTACHMENT SHOULD BE NAILS - SEE FBC
 2304.10.1 - 8D COMMON OR DEFORMED (21/2? ? 0.131?)
 (ROOF) OR RSRS-01 (23/8? ? 0.113?) NAIL (ROOF)D