| Plan Review Notes For Permit 22051346 |
| Permit Number |
22051346 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-22 16:25:14 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING ALS1.1 AND A1.1.1 SHOW AN ADDED UTILITY ROOM | | | WITH A DOOR THAT APPEARS TO ENCROACH ON THE EGRESS | | | WIDTH - FBC 1005.7.1 DOORS. | | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | | THAN ONE-HALF. | | | | | | 2) DOORS MARKED 105 C AND 105 D NEED TO BE SHOWN ON THE | | | DOOR SCHEDULE - SIZES, FIRE RATINGS, SELF CLOSING ETC. | | | | | | 3) DOOR 105 D SHOWS TO BE PART OF A FIRE WALL - PLEASE | | | SHOW THE HOURLY FIRE RATINGS AND SELF CLOSING/LATCHING | | | - FBC 716.5 AND 716.5.9 | | | | | | 4) DRAWING A1.1.1 - MAYBE THE FIRE RATED WALL IS SHOWN | | | INCORRECTLY FOR THE UTILITY ROOM IN UNIT 423. |
|