Plan Review Notes
Plan Review Notes For Permit 22051346
Permit Number 22051346
Review Stop B
Sequence Number 1
Notes
Date Text
2022-06-22 16:25:14REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING ALS1.1 AND A1.1.1 SHOW AN ADDED UTILITY ROOM
 WITH A DOOR THAT APPEARS TO ENCROACH ON THE EGRESS
 WIDTH - FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 2) DOORS MARKED 105 C AND 105 D NEED TO BE SHOWN ON THE
 DOOR SCHEDULE - SIZES, FIRE RATINGS, SELF CLOSING ETC.
  
 3) DOOR 105 D SHOWS TO BE PART OF A FIRE WALL - PLEASE
 SHOW THE HOURLY FIRE RATINGS AND SELF CLOSING/LATCHING
 - FBC 716.5 AND 716.5.9
  
 4) DRAWING A1.1.1 - MAYBE THE FIRE RATED WALL IS SHOWN
 INCORRECTLY FOR THE UTILITY ROOM IN UNIT 423.