| Plan Review Notes For Permit 22051345 |
| Permit Number |
22051345 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-06 09:16:21 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. [ THE SIGNED AND SEALED WINDLOAD | | | CALCULATIONS THAT WERE SUBMITTED DO NOT INCLUDE THE | | | POLE, THE POLE BASE OR THE ANCHORS.] SUBMIT SIGNED AND | | | SEALED WIND LOAD CALCULATIONS FROM A FLORIDA LICENSED | | | DESIGN PROFESSIONAL FOR THE PROPOSED LIGHT POLES. FBC | | | 1603.1.4 | | | | | | 2) NOT RESOLVED. [ THE FOUNDATION DRAWING IS OKAY, | | | HOWEVER, THE ANCHORING DETAILS WERE NOT ADDRESSED.] | | | SUBMIT FOUNDATION AND ANCHORING DETAILS FOR THE | | | PROPOSED LIGHT POLES. FBC 1604.8 | | | | | | 3) SEE SIGNATURE REVIEW. |
|