| Plan Review Notes For Permit 22051343 |
| Permit Number |
22051343 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-23 11:49:41 | 1ST REVIEW FMC | | | PERMIT: 22051343 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE OUTDOOR AIR CALCULATIONS BASED ON EACH | | | OCCUPANCY CLASSIFICATION IN THIS TENANT SPACE ACCORDING | | | TO FMC TABLE 403.3.1.1. THERE ARE TRAINING ROOMS, | | | CONFERENCE ROOMS STORAGE ROOMS AND A COPY ROOM IN THIS | | | TENANT SPACE. | | | | | | 2) PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL | | | SYSTEMS. FBC 107.2.1 | | | | | | 3) THE ENERGY CALCULATIONS DO NOT MATCH THE MECHANICAL | | | DRAWINGS. IS THERE ANY MECHANICAL UNITS BEING ADDED? | | | THE ENERGY CALCULATIONS ARE CALLING FOR BOTH RTU?S AND | | | AHU?S. THE ENERGY CALCULATIONS SHOW THE WAREHOUSE TO BE | | | UNCONDITIONED. | | | | | | 4) EXPLAIN THE NEW EF-4. FBC 107.2.1 | | | | | | 5) IS THE WALL SEPARATING THE OFFICE SPACE FROM THE | | | WAREHOUSE A RATED WALL? FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|