| 2022-07-27 13:31:41 | AUDITORIUM RENOVATION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING A-2 PLEASE SHOW THE SOFFIT FRAMING |
| | ATTACHMENT TO THE EXISTING STRUCTURE - ATTACHMENT TYPE, |
| | SIZE AND OC SPACING FBC WPB 107.2 |
| | |
| | 2) WALLS SEPARATING STAGE FROM BACK ROOMS - STORAGE AND |
| | DRESSING ROOMS - SHOULD BE FIRE RATED PER FBC 410.5.1 |
| | SEPARATION FROM STAGE. |
| | THE STAGE SHALL BE SEPARATED FROM DRESSING ROOMS, SCENE |
| | DOCKS, PROPERTY ROOMS, WORKSHOPS, STOREROOMS AND |
| | COMPARTMENTS APPURTENANT TO THE STAGE AND OTHER PARTS |
| | OF THE BUILDING BY FIRE BARRIERS CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH. |
| | THE FIRE-RESISTANCE RATING SHALL BE NOT LESS THAN 2 |
| | HOURS FOR STAGE HEIGHTS GREATER THAN 50 FEET (15 240 |
| | MM) AND NOT LESS THAN 1 HOUR FOR STAGE HEIGHTS OF 50 |
| | FEET (15 240 MM) OR LESS. |
| | |
| | 3) WALLS SEPARATING STORAGE FROM DRESSING ROOM SHOULD |
| | BE FIRE RATED PER FBC 410.5.2 SEPARATION FROM EACH |
| | OTHER. |
| | DRESSING ROOMS, SCENE DOCKS, PROPERTY ROOMS, WORKSHOPS, |
| | STOREROOMS AND COMPARTMENTS APPURTENANT TO THE STAGE |
| | SHALL BE SEPARATED FROM EACH OTHER BY NOT LESS THAN |
| | 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 711, OR BOTH. |