| Plan Review Notes For Permit 22051284 |
| Permit Number |
22051284 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-12 17:47:59 | ROOFING REVIEW: | | | | | | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | | | ORIGINAL COMMENT: | | | A)OK. | | | | | | B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01 | | | SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT | | | APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT | | | ABOVE. | | | | | | RESPONSE: | | | REPEAT COMMENT. SAME NOA WAS SUBMITTED. | | | | | | ORIGINAL COMMENT: | | | C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS | | | SPECIFIED ON PLANS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | COORDINATE WITH ITEM ABOVE | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|