| 2022-12-12 17:30:32 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22051284 |
| | 201 SUMMA ST |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY. |
| | |
| | ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE BOTTOM |
| | OF FORM BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING |
| | THE PERMIT |
| | |
| | |
| | 1-OK. |
| | 2-OK. |
| | 3-OK. |
| | |
| | ORIGINAL COMMENT |
| | 4- SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING |
| | COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. |
| | NOTE: MAKE SURE THERE IS ENOUGH HEADROOM ABOVE ATTIC |
| | ACCESS PANEL. |
| | |
| | RESPONSE: |
| | ROOF FRAMING PLAN NEEDS TO BE REVISED TO ALLOW FOR THE |
| | ATTIC ACCESS PROPOSED LOCATION AND SIZE. ALSO, IT LOOKS |
| | LIKE THE PROPOSED LOCATION MAY NOT PROVIDE THE REQUIRED |
| | HEADROOM CLEARANCE. PROVIDE DETAIL SHOWING THE ACTUAL |
| | HEADROOM ON THE PROPOSED LOCATION. |
| | |
| | 5- ENLARGED STAIR PLAN DETAIL 2 ON SHEET A-501: |
| | ORIGINAL COMMENT: |
| | B)PROVIDE STAIR NOSING DETAIL SHOWING COMPLIANCE WITH |
| | SEC. R311.7.5.3 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | TREAD DIMENSION SHOWN ON DETAIL 10 DOESN'T MATCH TREAD |
| | DIMENSION SHOWN ON DETAIL 2. REVISE AS REQUIRED TO |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 6- ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING |
| | SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL |
| | SPECIFICATIONS. REVISED NAIL SPACING SPECIFIED IN ALL |
| | DETAILS AND SPECIFICATIONS SUBMITTED TO COMPLY TABLE |
| | R803.2.3.1 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" O.C. |
| | NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS |
| | SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR |
| | EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM |
| | REQUIREMENTS. |
| | |
| | RESPONSE: |
| | ROOF NOTE #1 ON SHEET S-2 WAS NOT REVISED. |
| | |
| | 7- OK. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)OK. |
| | |
| | ORIGINAL COMMENT: |
| | B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01 |
| | SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT |
| | APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT |
| | ABOVE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. SAME NOA WAS SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED AS |
| | SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D)OK. |
| | |
| | ORIGINAL COMMENT: |
| | E)STRUCTURAL MULLIONS AS SHOWN ON PLANS. AND REQUIRED: |
| | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. |
| | NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | CORRESPONDING TO DRAWINGS SUBMITTED. |
| | |
| | RESPONSE: |
| | CLEARLY SPECIFY OR MARK MULLION SIZE ON NOA 20-0406.03 |
| | SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | F)NEW OUTSIDE OUTSWING DOOR IN EXISTING LIVING ROOM |
| | AREA. |
| | NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | CORRESPONDING TO DRAWINGS SUBMITTED. |
| | |
| | RESPONSE: |
| | PROVIDE COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. |
| | NOTE: THERE ARE SEVERAL DOOR PRODUCT APPROVALS |
| | SUBMITTED. CLEARLY LABEL EACH PRODUCT APPROVAL LIKE |
| | ENTRY DOOR, STORAGE, LIVING ROOM, ETC TO AVOID |
| | CONFLICTS/DELAYS. PLEASE COORDINATE WITH THE PERMIT |
| | LIBRARIAN TO SEE WHICH PRODUCT APPROVALS YOU WANT TO BE |
| | DELETED. |
| | |
| | ORIGINAL COMMENT: |
| | G)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE. |
| | NOTE: NEED TO PROVIDE COMPLETE PRODUCT APPROVAL, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| | CORRESPONDING TO DRAWINGS SUBMITTED. |
| | |
| | RESPONSE: |
| | COORDINATE WITH ITEM ABOVE. |
| | |
| | ORIGINAL COMMENT: |
| | H)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL NEXT |
| | TO THE NEW STAIRWAY. |
| | |
| | RESPONSE: |
| | COORDINATE WITH ITEM ABOVE. |
| | |
| | ORIGINAL COMMENT: |
| | 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | COORDINATE WITH ITEM ABOVE. |
| | |
| | 10- ENERGY CALCULATIONS SUBMITTED: |
| | ORIGINAL COMMENT: |
| | A) THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B)OK. |
| | C)OK. |
| | |
| | ORIGINAL COMMENT: |
| | D)IT IS NOT CLEAR IF THE CALCULATIONS ARE DONE FOR THE |
| | ENTIRE HOUSE OR JUST THE ADDITION. CALCULATIONS CAN BE |
| | DONE EITHER WAY, BUT THEY NEED TO BE CONSISTENT. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NOT CLEAR. CONDITIONED FLOOR AREA ON ITEM 6 OF |
| | PAGE ONE DOESN'T MATCH A/C AREAS SHOWN ON PLANS. SHEET |
| | G-001. |
| | |
| | ORIGINAL COMMENT: |
| | E)REVISE/CLARIFY ITEM #1 ON PAGE ONE. EXISTING OR NEW |
| | CONSTRUCTION (ADDITION). COORDINATE WITH COMMENT (D) |
| | ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | F)REVISE/CLARIFY ITEM #4 ON PAGE ONE. PROVIDE CORRECT |
| | NUMBER OF BEDROOMS. COORDINATE WITH COMMENT (D)ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | G)REVISE/CLARIFY ITEM #6 ON PAGE ONE. PROVIDE CORRECT |
| | CONDITIONED FLOOR AREA. SEE PLANS AND COORDINATE WITH |
| | COMMENT (D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | H)REVISE/CLARIFY ITEM #11 ON PAGE ONE. PLANS SHOW |
| | UNVENTED ATTIC AND THEY SHOW DIFFERENT R-VALUES FOR |
| | CEILING INSULATION DEPENDING ON THE ROOF TYPE. SEE |
| | PLANS AND REVISE AS REQUIRED. AND COORDINATE WITH |
| | COMMENT (D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | CEILING INSULATION DOESN'T MATCH PLANS. SEE SHEETS |
| | A-400 AND A-401 AND REVISE AS REQUIRED. |
| | |
| | I)OK. |
| | |
| | ORIGINAL COMMENT: |
| | J)REVISE/CLARIFY PROJECT INFORMATION ON PAGE 2. TWO |
| | STORY ONLY APPLIES IF ENTIRE HOUSE IS CONSIDERED. |
| | ADDITION ALONE IS ONE STORY. SEE PLANS AND COORDINATE |
| | WITH COMMENT (D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | K)REVISE/CLARIFY SPACES INFORMATION ON PAGE 2. KITCHEN |
| | ONLY APPLIES TO ENTIRE HOUSE. SEE PLANS AND REVISE AS |
| | REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | L)REVISE/CLARIFY ROOF TYPE INFORMATION ON PAGE 2. IT |
| | LOOKS LIKE THERE ARE MORE GABLES IN THIS HOUSE. AND IS |
| | MISSING THE ROOF AREA. SEE PLANS AND REVISE AS |
| | REQUIRED. AND COORDINATE WITH COMMENT (D) ABOVE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | NOTE: THERE ARE GABLE ROOFS IN THIS HOUSE ALSO. PROVIDE |
| | REQUIRED INFORMATION. |
| | |
| | M)OK. |
| | |
| | ORIGINAL COMMENT: |
| | N)REVISE/CLARIFY DOORS INFORMATION ON PAGE 3. WHERE ARE |
| | THE WOOD DOORS ON THE NORTH AND SOUTH SIDE? SEE PLANS |
| | AND REVISE AS REQUIRED. AND COORDINATE WITH COMMENT (D) |
| | ABOVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | NOTE: PLANS DON'T SHOW WOOD DOORS. |
| | |
| | ORIGINAL COMMENT: |
| | O)REVISE/CLARIFY WINDOWS INFORMATION ON PAGE 3. REVISE |
| | WINDOWS AREA, AND OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. AND |
| | COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | NOTE: WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH |
| | PLANS. SEE ELEVATIONS. |
| | |
| | ORIGINAL COMMENT: |
| | P)REVISE/CLARIFY GARAGE INFORMATION ON PAGE 3. |
| | COORDINATE WITH COMMENT (D) ABOVE. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STILL NO CLEAR. COORDINATE WITH COMMENT (D)ABOVE TO |
| | AVOID MORE CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | Q)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | NO ADDRESSED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |