| 2022-07-26 16:08:20 | ROOFING REVIEW: |
| | |
| | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ROOF TILE. NOA 18-0509.17 SUBMITTED EXPIRED ON |
| | 04/26/22. NEED CURRENT PRODUCT APPROVAL. |
| | ALSO, CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED AS |
| | REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: ROOF TILE ADHESIVE PRODUCT APPROVAL SUBMITTED IS |
| | FOR TILE BOND. ACCORDING TO ROOF TILE NOA THE MINIMUM |
| | ATTACHMENT RESISTANCE USING TILE BOND ADHESIVE IS |
| | 31.3FT-LBF. ACCORDING TO FRSA MANUAL THE MINIMUM |
| | REQUIRED UPLIFT MOMENT FOR TILE AT HIS HOUSE IS MORE |
| | THAN 31.3FT-LBF. NEED TO SPECIFY OTHER TILE ADHESIVE |
| | THAT MEETS OR EXCEEDS THE MINIMUM REQUIRED UPLIFT |
| | MOMENT FOR TILE. OR PROVIDE CALCULATIONS SHOWING |
| | COMPLIANCE WITH TILE BOND ADHESIVE. |
| | |
| | NOTE; THERE ARE TWO DIFFERENT ROOF TILE NOA'S |
| | SUBMITTED. CLARIFY WHICH ONE IS GOING TO BE USED TO |
| | AVOID CONFLICTS/DELAYS. |
| | |
| | B)ROOF TILE ADHESIVE. TILE BOND NOA 16-0222.01 |
| | SUBMITTED EXPIRED ON 08/23/21. NEED CURRENT PRODUCT |
| | APPROVAL. ALSO, COORDINATE WITH ROOF TILE COMMENT |
| | ABOVE. |
| | |
| | C)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| | |
| | D)TERRACE UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED |
| | WITH FINISH FLOOR SPECIFIED ON PLANS. DESIGNER OF |
| | RECORD TO PROVIDE SPECIFICATIONS FOR FINISH FLOORING. |
| | NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE |
| | INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED IF |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ZONES. |
| | |
| | 2-- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |