| 2022-08-24 12:28:00 | SIMPLIFIED COMMENTS |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 315.1 - PLEASE ADD TO YOUR FIRE STOPPING |
| | DETAILS PROVISIONS FOR PVC PENETRATIONS. IT APPEARS |
| | THAT ALL OF THEM ARE FOR "METALLIC" PIPE. MAKE SURE YOU |
| | HAVE A UL RATED LISTING FOR EACH TYPE OF PIPE |
| | PENETRATION. THE INSPECTOR WILL NEED THESE AND HAVING |
| | THEM SUBMITTED NOW WILL SAVE TIME WITH REVISIONS LATER. |
| | |
| | 2. 2020 FEC TABLE C403.2.10 - CHANGE NOTE 14 TO STATE |
| | THE MINIMUM PIPE INSULATION THICKNESS IS 1", NOT 1/2". |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - YOU'VE SPEC'D OUT TOILETS |
| | THAT ARE 10.5" TALL. CAN YOU CLARIFY THAT THESE ARE FOR |
| | CHILDREN? IF NOT, CHANGE THE TOILET SPECIFICATION. |
| | ALSO, PLEASE CORRECT THE TAGS ON THE RISER DIAGRAMS TO |
| | CORRESPOND WITH THE ACTUAL FIXTURES INSTALLED. |
| | |
| | 4. 2020 FPC TABLE 709.1 - THE RISER SHOWS A TRAP SIZE |
| | OF 1" FOR THE FLOOR DRAIN. THE MINIMUM TRAP SIZE IS 2", |
| | PLEASE CHANGE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |