| 2022-08-23 16:55:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22051265 300 PEMBROKE PL |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 8. THIRD REQUEST:P-05/PLUMBING NOTES: PER WPB FBC |
| | 107.2.1, REVISE THE FOLLOWING |
| | ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE |
| | AND FITTINGS" ORIGINAL NOTE 7 ADDRESSED SANITARY PIPE |
| | SPECIFICATIONS WHICH WAS PVC SCHEDULE 40 PIPE AND |
| | FITTINGS. NOTE 7 NOW ADDRESSES CONDENSATE PIPE; PROVIDE |
| | SANITARY DWV DRAINAGE PIPING SPECIFICATION. PLEASE NOTE |
| | THAT P-10 AND P-11 DETAILS DO NOT PROVIDE A RATED |
| | ASSEMBLY FOR PVC THROUGH THE FLOOR PENETRATIONS AND IF |
| | PVC IS TO BE USED A RATED ASSEMBLY SHALL BE PROVIDED. |
| | ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN |
| | ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE |
| | C403.2.10" TABLE C403.2.10 INDICATES MINIMUM THICKNESS |
| | SHALL BE 1" NOT 1/2" AS NOTED IN NEW NOTE 14 WHICH |
| | CALLS FOR 1/2 " ARMAFLEX; MAKE CORRECTION. PROVISION |
| | FOR WATER HAMMER ARRESTORS TO COMPLY WITH ASSE 1010 PER |
| | 604.9 IS CORRECT. |
| | |
| | 10. THIRD REQUEST: PARTIALLY COMPLIED. RESPONSE WAS |
| | LISTED ON P-05, NOTE 29(A), (B) P-05; NO DETAIL WAS |
| | PROVIDED PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION |
| | SHOWER WALL/FLOOR/DRAIN AND THRESHOLD DETAIL. |
| | |
| | 13. THIRD REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | APPLICABLE RATED WALL/FLOOR DETAILS FOR PLUMBING |
| | PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC |
| | CHAPTER 7. PARTIALLY COMPLIED. SEE COMMENT 8/***A) |
| | NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE AND |
| | FITTINGS" ORIGINAL NOTE 7 ADDRESSED SANITARY PIPE |
| | SPECIFICATIONS WHICH WAS PVC SCHEDULE 40 PIPE AND |
| | FITTINGS. NOTE 7 NOW ADDRESSES CONDENSATE PIPE; PROVIDE |
| | SANITARY DWV DRAINAGE PIPING SPECIFICATION. PLEASE NOTE |
| | THAT P-10 AND P-11 DETAILS DO NOT PROVIDE A RATED |
| | ASSEMBLY FOR PVC THROUGH THE FLOOR PENETRATIONS AND IF |
| | PVC IS TO BE USED A RATED ASSEMBLY SHALL BE PROVIDED. |
| | |
| | 18. THIRD REQUEST: P-01/EXISTING FLOOR DRAIN: PER WPB |
| | FBC 107.2.1, CONFIRM THAT THE EXISTING FLOOR DRAIN IN |
| | THE NEW BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE |
| | PLAN HOW IT IS PROVIDED. IF NOT, THEN PER FBC PL |
| | 1002.4.1, PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE |
| | WITH ONE OF THE METHODS IN SECTIONS 1002.4.1.1 THROUGH |
| | 1002.4.1.4. ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL. |
| | RESPONSE REFERENCES NEW FIXTURE SCHEDULE BUT NOTED |
| | FLOOR DRAIN DOES NOT CORRESPOND WITH FIXTURE SCHEDULE. |
| | PLEASE SHOW TRAP PIMER CONNECTION TO FLOOR DRAIN AND |
| | PROVIDE SPEC AND DETAIL |
| | |
| | 20. THIRD REQUEST: P-05/SANITARY RISER SERVICING ONLY |
| | FLOORS 2 THROUGH 4: PER FBC PL 912.1.1, THE SHOWER |
| | DRAIN ON THE FOURTH FLOOR SHALL CONNECT TO THE STACK AT |
| | OR ABOVE THE WATER CLOSET ELEVATION. PLEASE NOTE ALSO |
| | THAT ANY TIME A WATER CLOSET AND OTHER BATHROOM GROUP |
| | FIXTURES ARE CONNECTED TO ANY VERTICAL WET VENT, THE |
| | OTHER FIXTURES SHALL CONNECT AT OR ABOVE THE ELEVATION |
| | WITH THE WATER CLOSET AS NOTED IN 912.1.1. CLARIFY; |
| | EACH BATHROOM GROUP ON SECOND AND THIRD FLOOR SHALL BE |
| | VENTED BEFORE CONNECTING TO THE STACK. THE SHOWER SHALL |
| | CONNECT AT OR ABOVE THE WATER CLOSET. |
| | |
| | 23. SECOND REQUEST: PER WPB FBC 107.2.1, ID/TAG THE |
| | SANITARY AND WATER RISERS ON BOTH RISER DIAGRAMS AND |
| | FLOOR PLANS. ID/TAG SHALL MATCH ON THE CORRESPONDING |
| | DRAWINGS. SEE COMMENT 7 REGARDING THE FIXTURE SCHEDULE. |
| | PARTIALLY COMPLIED |
| | NEW COMMENTS |
| | ***A) REGARDING THE WATER CLOSETS, P-06 SANITARY RISERS |
| | SHOWS WC-2/A.S. 2315228 10-1/4 INCH HIGH BOWL ON RISER |
| | SERVICING ONLY FLOORS 2, 3 AND 4; WC-1/KOHLER 3544EB |
| | HANDICAP ARE SHOWN ON RISER SERVICING FLOORS 1, 2, 3 |
| | AND 4. P-01 AND P-02 FLOOR PLANS SHOW WC-2/A.S. 2315228 |
| | 10-1/4 INCH HIGH BOWL IN ALL LOCATIONS |
| | ***B) REGARDING THE LAVATORIES, P-06 SANITARY RISERS |
| | SHOWS L-3/A.S.0614000 UNDERMOUNT ON RISER SERVICING |
| | ONLY FLOORS 2, 3 AND 4; L-1/KOHLER 2032 WALL HUNG ARE |
| | SHOWN ON RISER SERVICING FLOORS 1, 2, 3 AND 4. P-01 AND |
| | P-02 FLOOR PLANS SHOW L-3/A.S.0614000 UNDERMOUNT IN ALL |
| | LOCATIONS. |
| | ***C) PER WPB FBC 107.2.1, PLEASE CLARIFY AND RECONCILE |
| | ***D) REGARDING THE FLOOR DRAIN, MINIMUM SIZE FLOOR |
| | DRAIN IS 2" PER FBC PL TABLE 709.1. P-06 SHOWS 1-1/2" |
| | SIZE; ADDITIONALLY, PROVIDE A P-TRAP ON DRAWING. |
| | |
| | 25. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE |
| | INDICATE ON THE PLANS IF THE HOT WATER SYSTEM IS |
| | RECIRCULATED OR HEAT TRACED; PROVIDE THE TEMPERATURE OF |
| | THE HOT WATER. |
| | TO BE CLEAR, PER FBC PL 607.2, THE DEVELOPED LENGTH OF |
| | HOT OR TEMPERED WATER PIPING FROM THE SOURCE OF HOT |
| | WATER TO THE FIXTURE SHALL NOT EXCEED 50 FEET. |
| | RECIRCULATING SYSTEMS AND HEAT TRACED SYSTEMS ARE |
| | CONSIDERED TO BE SOURCES OF HOT OR TEMPERED WATER. |
| | PLEASE SHOW THAT THE HOT OR TEMPERED WATER FROM THE |
| | SOURCE TO THE FIXTURES DOES NOT EXCEED 50 FEET OR |
| | PROVIDE MEANS TO COMPLY. PARTIALY COMPLIED |
| | P-07/WATER RISER DISTRIBUTION NOTES A CLOSED LOOP |
| | RECIRCULATION BETWEEN THE WATER HEATER AND A HOT WATER |
| | STORAGE TANK WITH A NON RECIRCULATED WATER LINE TO HOT |
| | WATER DISTRIBUTION. PER FBC PL 607.2 AND FBC RES |
| | P2601.1, THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| | PIPING FROM THE SOURCE OF HOT WATER TO THE FIXTURE |
| | SHALL NOT EXCEED 50 FEET. RECIRCULATING SYSTEMS AND |
| | HEAT TRACED SYSTEMS ARE CONSIDERED TO BE SOURCES OF HOT |
| | OR TEMPERED WATER. PLEASE SHOW THAT THE HOT OR TEMPERED |
| | WATER FROM THE SOURCE TO THE FIXTURES DOES NOT EXCEED |
| | 50 FEET OR PROVIDE MEANS TO COMPLY. |
| | PER WPB FBC 107.2.1, PROVIDE A COMPLIANT SYSTEM. PLEASE |
| | NOTE THAT A TANKLESS WATER HEATER CAPABLE OF SUPPORTING |
| | ADEQUATE HOT WATER DEMAND IN EACH NEW BATHROOM IS |
| | CONSIDERED AN ADEQUATE SOURCE OF HOT WATER. THE UNIT |
| | WOULD REQUIRE A SCHEDULE WITH GPM AND ELECTRICAL |
| | CHARACTERISTICS. LOCATION(S) ON FLOOR PLANS, RISER |
| | DIAGRAM AND A DETAIL WOULD BE REQUIRED. ADDITIONALLY, A |
| | NEW ELECTRICAL REVIEW WOULD BE REQUIRED. |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | PLEASE PROVIDE A DETAILED RESPONSE LETTER ADDRESING |
| | EACH ITEM/COMMENT. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |