2022-08-23 16:55:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22051265 300 PEMBROKE PL
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
  
 8. THIRD REQUEST:P-05/PLUMBING NOTES: PER WPB FBC
 107.2.1, REVISE THE FOLLOWING
 ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE
 AND FITTINGS" ORIGINAL NOTE 7 ADDRESSED SANITARY PIPE
 SPECIFICATIONS WHICH WAS PVC SCHEDULE 40 PIPE AND
 FITTINGS. NOTE 7 NOW ADDRESSES CONDENSATE PIPE; PROVIDE
 SANITARY DWV DRAINAGE PIPING SPECIFICATION. PLEASE NOTE
 THAT P-10 AND P-11 DETAILS DO NOT PROVIDE A RATED
 ASSEMBLY FOR PVC THROUGH THE FLOOR PENETRATIONS AND IF
 PVC IS TO BE USED A RATED ASSEMBLY SHALL BE PROVIDED.
 ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN
 ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE
 C403.2.10" TABLE C403.2.10 INDICATES MINIMUM THICKNESS
 SHALL BE 1" NOT 1/2" AS NOTED IN NEW NOTE 14 WHICH
 CALLS FOR 1/2 " ARMAFLEX; MAKE CORRECTION. PROVISION
 FOR WATER HAMMER ARRESTORS TO COMPLY WITH ASSE 1010 PER
 604.9 IS CORRECT.
  
 10. THIRD REQUEST: PARTIALLY COMPLIED. RESPONSE WAS
 LISTED ON P-05, NOTE 29(A), (B) P-05; NO DETAIL WAS
 PROVIDED PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION
 SHOWER WALL/FLOOR/DRAIN AND THRESHOLD DETAIL.
  
 13. THIRD REQUEST: PER WPB FBC 107.2.1, PROVIDE
 APPLICABLE RATED WALL/FLOOR DETAILS FOR PLUMBING
 PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC
 CHAPTER 7. PARTIALLY COMPLIED. SEE COMMENT 8/***A)
 NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE AND
 FITTINGS" ORIGINAL NOTE 7 ADDRESSED SANITARY PIPE
 SPECIFICATIONS WHICH WAS PVC SCHEDULE 40 PIPE AND
 FITTINGS. NOTE 7 NOW ADDRESSES CONDENSATE PIPE; PROVIDE
 SANITARY DWV DRAINAGE PIPING SPECIFICATION. PLEASE NOTE
 THAT P-10 AND P-11 DETAILS DO NOT PROVIDE A RATED
 ASSEMBLY FOR PVC THROUGH THE FLOOR PENETRATIONS AND IF
 PVC IS TO BE USED A RATED ASSEMBLY SHALL BE PROVIDED.
  
 18. THIRD REQUEST: P-01/EXISTING FLOOR DRAIN: PER WPB
 FBC 107.2.1, CONFIRM THAT THE EXISTING FLOOR DRAIN IN
 THE NEW BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE
 PLAN HOW IT IS PROVIDED. IF NOT, THEN PER FBC PL
 1002.4.1, PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE
 WITH ONE OF THE METHODS IN SECTIONS 1002.4.1.1 THROUGH
 1002.4.1.4. ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL.
 RESPONSE REFERENCES NEW FIXTURE SCHEDULE BUT NOTED
 FLOOR DRAIN DOES NOT CORRESPOND WITH FIXTURE SCHEDULE.
 PLEASE SHOW TRAP PIMER CONNECTION TO FLOOR DRAIN AND
 PROVIDE SPEC AND DETAIL
  
 20. THIRD REQUEST: P-05/SANITARY RISER SERVICING ONLY
 FLOORS 2 THROUGH 4: PER FBC PL 912.1.1, THE SHOWER
 DRAIN ON THE FOURTH FLOOR SHALL CONNECT TO THE STACK AT
 OR ABOVE THE WATER CLOSET ELEVATION. PLEASE NOTE ALSO
 THAT ANY TIME A WATER CLOSET AND OTHER BATHROOM GROUP
 FIXTURES ARE CONNECTED TO ANY VERTICAL WET VENT, THE
 OTHER FIXTURES SHALL CONNECT AT OR ABOVE THE ELEVATION
 WITH THE WATER CLOSET AS NOTED IN 912.1.1. CLARIFY;
 EACH BATHROOM GROUP ON SECOND AND THIRD FLOOR SHALL BE
 VENTED BEFORE CONNECTING TO THE STACK. THE SHOWER SHALL
 CONNECT AT OR ABOVE THE WATER CLOSET.
  
 23. SECOND REQUEST: PER WPB FBC 107.2.1, ID/TAG THE
 SANITARY AND WATER RISERS ON BOTH RISER DIAGRAMS AND
 FLOOR PLANS. ID/TAG SHALL MATCH ON THE CORRESPONDING
 DRAWINGS. SEE COMMENT 7 REGARDING THE FIXTURE SCHEDULE.
 PARTIALLY COMPLIED
 NEW COMMENTS
 ***A) REGARDING THE WATER CLOSETS, P-06 SANITARY RISERS
 SHOWS WC-2/A.S. 2315228 10-1/4 INCH HIGH BOWL ON RISER
 SERVICING ONLY FLOORS 2, 3 AND 4; WC-1/KOHLER 3544EB
 HANDICAP ARE SHOWN ON RISER SERVICING FLOORS 1, 2, 3
 AND 4. P-01 AND P-02 FLOOR PLANS SHOW WC-2/A.S. 2315228
 10-1/4 INCH HIGH BOWL IN ALL LOCATIONS
 ***B) REGARDING THE LAVATORIES, P-06 SANITARY RISERS
 SHOWS L-3/A.S.0614000 UNDERMOUNT ON RISER SERVICING
 ONLY FLOORS 2, 3 AND 4; L-1/KOHLER 2032 WALL HUNG ARE
 SHOWN ON RISER SERVICING FLOORS 1, 2, 3 AND 4. P-01 AND
 P-02 FLOOR PLANS SHOW L-3/A.S.0614000 UNDERMOUNT IN ALL
 LOCATIONS.
 ***C) PER WPB FBC 107.2.1, PLEASE CLARIFY AND RECONCILE
 ***D) REGARDING THE FLOOR DRAIN, MINIMUM SIZE FLOOR
 DRAIN IS 2" PER FBC PL TABLE 709.1. P-06 SHOWS 1-1/2"
 SIZE; ADDITIONALLY, PROVIDE A P-TRAP ON DRAWING.
  
 25. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE
 INDICATE ON THE PLANS IF THE HOT WATER SYSTEM IS
 RECIRCULATED OR HEAT TRACED; PROVIDE THE TEMPERATURE OF
 THE HOT WATER.
 TO BE CLEAR, PER FBC PL 607.2, THE DEVELOPED LENGTH OF
 HOT OR TEMPERED WATER PIPING FROM THE SOURCE OF HOT
 WATER TO THE FIXTURE SHALL NOT EXCEED 50 FEET.
 RECIRCULATING SYSTEMS AND HEAT TRACED SYSTEMS ARE
 CONSIDERED TO BE SOURCES OF HOT OR TEMPERED WATER.
 PLEASE SHOW THAT THE HOT OR TEMPERED WATER FROM THE
 SOURCE TO THE FIXTURES DOES NOT EXCEED 50 FEET OR
 PROVIDE MEANS TO COMPLY. PARTIALY COMPLIED
 P-07/WATER RISER DISTRIBUTION NOTES A CLOSED LOOP
 RECIRCULATION BETWEEN THE WATER HEATER AND A HOT WATER
 STORAGE TANK WITH A NON RECIRCULATED WATER LINE TO HOT
 WATER DISTRIBUTION. PER FBC PL 607.2 AND FBC RES
 P2601.1, THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING FROM THE SOURCE OF HOT WATER TO THE FIXTURE
 SHALL NOT EXCEED 50 FEET. RECIRCULATING SYSTEMS AND
 HEAT TRACED SYSTEMS ARE CONSIDERED TO BE SOURCES OF HOT
 OR TEMPERED WATER. PLEASE SHOW THAT THE HOT OR TEMPERED
 WATER FROM THE SOURCE TO THE FIXTURES DOES NOT EXCEED
 50 FEET OR PROVIDE MEANS TO COMPLY.
 PER WPB FBC 107.2.1, PROVIDE A COMPLIANT SYSTEM. PLEASE
 NOTE THAT A TANKLESS WATER HEATER CAPABLE OF SUPPORTING
 ADEQUATE HOT WATER DEMAND IN EACH NEW BATHROOM IS
 CONSIDERED AN ADEQUATE SOURCE OF HOT WATER. THE UNIT
 WOULD REQUIRE A SCHEDULE WITH GPM AND ELECTRICAL
 CHARACTERISTICS. LOCATION(S) ON FLOOR PLANS, RISER
 DIAGRAM AND A DETAIL WOULD BE REQUIRED. ADDITIONALLY, A
 NEW ELECTRICAL REVIEW WOULD BE REQUIRED.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A DETAILED RESPONSE LETTER ADDRESING
 EACH ITEM/COMMENT.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  