| Notes |
| Date |
Text |
| 2022-08-25 09:21:38 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 3.) FBC B 107.2.1/FBC B 107.3.4.1, THE PROPOSED | | | FLOORING/FLOORING UNDERLAYMENT TEST REPORTS ARE | | | REQUIRED FOR: | | | A.) SOUND TRANSMISSION (NOT LESS THAN 50) ASTM E-90. | | | B.) IMPACT INSULATION (NOT LESS THAN 50) ASTM E-492. | | | C.) FLAME SPREAD SPECIFICATION (NOT MORE THAN 200) ASTM | | | E-84. | | | | | | FBC B 107.3.4.1, IF THE INTENTION IS TO DEFER THESE | | | SUBMITTALS, PLEASE LIST THESE SUBMITTAL ITEMS ON THE | | | CONSTRUCTION DOCUMENTS/PLANS. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. |
|