2022-07-19 15:35:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22051265 300 PEMBROKE PL
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 RESPONSE AND/OR CORRECTIONS IN RESPONSE TO THE FIRST
 REVIEW WERE NOT PROVIDED BY THE DESIGN PROFESSIONAL(S).
 IN ADDITION TO THE ORIGINAL COMMENTS, NEW COMMENTS HAVE
 BEEN ADDED. IT IS IMPORTANT THAT ALL COMMENTS ARE
 RESPONDED TO, AND CORRECTIONS MADE FOR APPROVAL. PLEASE
 BE SURE TO PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT, NOTING THE PLAN PAGE SHOWING THE CORRECTIONS.
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. SECOND REQUEST: PLEASE NOTE FBC ACC 202.4.1,
 DISPROPORTIONATE COST: ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 TO BE CLEAR, A RESPONSE IS REQUIRED.
  
 ***A) PER WPB FBC 107.2.1, PROVIDE DIMENSIONED PLAN AND
 ELEVATION VIEW OF EXISTING MEN AND WOMEN TOILET ROOMS
 SHOWING COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6 AS
 FOLLOWS:
 *****1) THE WATER CLOSET SHALL BE POSITIONED WITH A
 WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 *****2) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1
 *****3) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 *****4) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 *****5) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 *****6) PER FBC ACC 604.8, TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS.
 *****7) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 *****8) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 *****9) LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER
 FBC ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE
 AS REQUIRED BY FBC ACC 306.2 AND 306.3
 *****10) PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
 *****11) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 *****12) MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 *****13) SHOW TURNING SPACE COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2.
 *****14) PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***B) PLEASE NOTE THE DRINKING FOUNTAIN ON PLAN SHEET
 A-01, P-01 AND THE REQUIREMENTS OF FBC ACC 211.1,
 211.2; WHERE DRINKING FOUNTAINS ARE PROVIDED, NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. PER
 WPB FBC 107.2.1, AN ELEVATION AND PLAN DETAIL OF THE
 UPGRADED FIXTURE(S) IS REQUIRED.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***C) PER WPB FBC 107.2.1, PROVIDE ELEVATION AND PLAN
 DETAIL FOR WASHER(S) AND DRYER(S) SHOWING COMPLIANCE
 WITH FBC ACC 214 AND 611. TOP LOADING MACHINES SHALL
 HAVE THE DOOR TO THE LAUNDRY COMPARTMENT LOCATED 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR. FRONT LOADING
 MACHINES SHALL HAVE THE BOTTOM OF THE OPENING TO THE
 LAUNDRY COMPARTMENT LOCATED 15 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***D) COST OF SUGGESTED UPGRADES IN EXCESS OF 20% OF
 THE COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA
 SHALL BE DEEMED DISPROPORTIONATE.
  
 2. SECOND REQUEST: WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3. PER WPB FBC 107.2.1, IDENTIFY
 ACCESSIBLE DORMITORY UNIT(S) AND PROVIDE ELEVATION AND
 PLAN DETAILS FOR NEW SINK SHOWING COMPLIANCE.
  
 3. SECOND REQUEST: PER FBC ACC 213.2, WHERE BATHING
 ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL COMPLY WITH
 603. PER WPB FBC 107.2.1, IDENTIFY ACCESSIBLE DORMITORY
 UNIT(S) AND PROVIDE ELEVATION AND PLAN DETAILS FOR NEW
 BATHING ROOM(S) SHOWING COMPLIANCE WITH FBC ACC 603.
 NEW COMMENT: SEE FBC ACC 809.4 FOR ADDED CLARIFICATION
 WHICH CLEARLY INDICATES REQUIREMENTS IN RESIDENTIAL
 DWELLING UNIT(S)
 213.3.2WATER CLOSETS.
 WHERE WATER CLOSETS ARE PROVIDED, AT LEAST ONE SHALL
 COMPLY WITH 604.
 213.3.4LAVATORIES.
 WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE SHALL
 COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A TOILET
 COMPARTMENT.
 213.3.5MIRRORS.
 WHERE MIRRORS ARE PROVIDED, AT LEAST ONE SHALL COMPLY
 WITH 603.3.
 213.3.6BATHING FACILITIES.
 WHERE BATHTUBS OR SHOWERS ARE PROVIDED, AT LEAST ONE
 BATHTUB COMPLYING WITH 607 OR AT LEAST ONE SHOWER
 COMPLYING WITH 608 SHALL BE PROVIDED.
  
 4. SECOND REQUEST: PLAN SHEET A-0/APPLICABLE CODES: PER
 WPB FBC 107.2.1, PLEASE ADD 2020 FLORIDA PLUMBING CODE
 7TH EDITION AND 2020 FLORIDA MECHANICAL CODE 7TH
 EDITION TO THE LIST OF APPLICABLE CODES.
  
 5. SECOND REQUEST: PLAN SHEET A-0/APPLICABLE CODES: PER
 FBC 310.4, THE OCCUPANCY FOR THIS FACILITY IS R-2
 RESIDENTIAL.
  
 6. SECOND REQUEST: PLAN SHEET A-01, A-02/CONSTRUCTION
 NOTE 4: PER WPB FBC 107.2.1, 107.3.5.1.3 AND 107.3.5.3,
 PLUMBING FIXTURE SPACING SHALL COMPLY WITH FLORIDA
 PLUMBING CODE 2020 7TH EDITION, NOT THE FLORIDA
 RESIDENTIAL CODE 2020 7TH EDITION
 ADDITIONALLY, AS NOTED IN COMMENT 3, COMPLY WITH FBC
 ACC 213.2 AND 809.4.
  
 7. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE IDENTIFY
 AND TAG ALL NEW PLUMBING FIXTURES ON PLUMBING FLOOR
 PLANS AND ISOMETRICS. TAG AND ID SHALL MATCH PLUMBING
 FIXTURE SCHEDULE ON P-05.
  
 8. SECOND REQUEST:P-05/PLUMBING NOTES: PER WPB FBC
 107.2.1, REVISE THE FOLLOWING
 ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE
 AND FITTINGS"
 ***B) NOTE 13 "COPPER WATER PIPING JOINTS TO BE MADE
 WITH LEAD FREE SOLDER"
 ***C) NOTE 14 "VALVES TO BE LEAD FREE"
 ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN
 ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE
 C403.2.10"
 PROVIDE A SPEC THAT COMPLIES
 ***E) NOTE 19 "IN ACCORDANCE WITH FBC PL 604.9, PROVIDE
 WATER HAMMER ARRESTORS AT EACH FIXTURE GROUP CONFORMING
 TO ASSE 1010"
 ***F) ADD NOTE "ALL COMPONENTS IN THE DOMESTIC WATER
 SYSTEM SHALL BE LEAD FREE IN ACCORDANCE WITH FBC PL
 605.2 AND 605.2.1"
  
 9. SECOND REQUEST: P-05/PLUMBING FIXTURE SCHEDULE: PER
 WPB FBC 107.2.1, PROVIDE SPEC AND ID/TAG FOR SHOWER.
 INCLUDE DRAIN, SHOWER CONTROL VALVE AND TRIM. PER FBC
 PL 412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE.
  
 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A
 CROSS-SECTION SHOWER WALL/FLOOR/DRAIN AND THRESHOLD
 DETAIL
 ***A) DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL
 421.5.2 AS FOLLOWS
 LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED
 BACKING
 LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT
 LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAIN
 LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET
 AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT
 BETWEEN THE LINER AND THE OUTLET
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 ***B) LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING
 WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED.
 ***C) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 ABOVE THE DRAIN OF THE SHOWER.
  
 11. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPE
 HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 12. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A SLAB
 REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE
 TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE
 SHALL BE ONSITE FOR FINAL INSPECTION.
  
 13. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 APPLICABLE RATED WALL/FLOOR DETAILS FOR PLUMBING
 PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC
 CHAPTER 7.
  
 14. SECOND REQUEST: PER WPB FBC 107.2.1, TO SHOW
 COMPLIANCE WITH FBC PL 704.1, PROVIDE NOTE STATING
 "HORIZONTAL DRAINAGE PIPING LESS THAN 3 INCH DIAMETER
 SHALL HAVE A MINIMUM SLOPE OF 1/4 INCH PER FOOT. 3 INCH
 TO 6 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF 1/8
 INCH PER FOOT".
  
 15. SECOND REQUEST: P-07/RISER DIAGRAM: PER FBC PL
 606.1(6) PROVIDE A FULL OPEN VALVE TO EACH HOT AND COLD
 WATER SUPPLY TO EACH NEW UNIT. THE LAVATORIES SHALL BE
 INSTALLED DOWNSTREAM OF SAID VALVES.
  
 16. SECOND REQUEST: P-07/RISER DIAGRAM: PER WPB FBC
 107.2.1, IDENTIFY THE WATER HAMMER ARRESTORS (TAG WHA)
 ON THE WATER RISER DIAGRAMS.
  
 17. SECOND REQUEST: PER FBC PL 604.1, THE DESIGN OF THE
 WATER DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED
 ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE
 PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER
 DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING
 SYSTEM IS AN APPROVED METHOD.
  
 18. SECOND REQUEST: P-01/EXISTING FLOOR DRAIN: PER WPB
 FBC 107.2.1, CONFIRM THAT THE EXISTING FLOOR DRAIN IN
 THE NEW BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE
 PLAN HOW IT IS PROVIDED. IF NOT, THEN PER FBC PL
 1002.4.1, PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE
 WITH ONE OF THE METHODS IN SECTIONS 1002.4.1.1 THROUGH
 1002.4.1.4. ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL.
  
 19. SECOND REQUEST: P-05/SANITARY RISER DIAGRAM: PER
 FBC PL 909.1, EACH FIXTURE TRAP SHALL HAVE A PROTECTING
 VENT LOCATED SO THAT THE SLOPE AND THE DEVELOPED LENGTH
 IN THE FIXTURE DRAIN FROM THE TRAP WEIR TO THE VENT
 FITTING ARE WITHIN THE REQUIREMENTS SET FORTH IN TABLE
 909.1. THE WATER CLOSETS AND SHOWERS ON THE FIRST,
 SECOND AND THIRD FLOORS DO NOT COMPLY. PER WPB FBC
 107.2.1, VENT EACH OF THE WATER CLOSETS AND SHOWERS IN
 ACCORDANCE WITH ONE OF THE PRESCRIBED METHODS IN
 CHAPTER 9.
  
 20. SECOND REQUEST: P-05/SANITARY RISER SERVICING ONLY
 FLOORS 2 THROUGH 4: PER FBC PL 912.1.1, THE SHOWER
 DRAIN ON THE FOURTH FLOOR SHALL CONNECT TO THE STACK AT
 OR ABOVE THE WATER CLOSET ELEVATION. PLEASE NOTE ALSO
 THAT ANY TIME A WATER CLOSET AND OTHER BATHROOM GROUP
 FIXTURES ARE CONNECTED TO ANY VERTICAL WET VENT, THE
 OTHER FIXTURES SHALL CONNECT AT OR ABOVE THE ELEVATION
 WITH THE WATER CLOSET AS NOTED IN 912.1.1.
  
 21. SECOND REQUEST: P-05/SANITARY RISER GROUND FLOOR:
 THE BRANCH BETWEEN THE FLOOR DRAIN AND THE CONNECTION
 RECEIVING THE BATHROOM GROUPS DISCHARGE IS INCORRECTLY
 TAGGED VTR. PER WPB FBC 107.2.1, PLEASE CORRECT.
  
 22. SECOND REQUEST: P-05/SANITARY RISER WITH GROUND
 FLOOR BATHROOM: WATER CLOSET FIXTURE DRAIN SHALL BE 3
 INCH MINIMUM SIZE PER FBC PL 704.2, TABLE 709.1(D) AND
 710.1(2)-A
  
 23. SECOND REQUEST: PER WPB FBC 107.2.1, ID/TAG THE
 SANITARY AND WATER RISERS ON BOTH RISER DIAGRAMS AND
 FLOOR PLANS. ID/TAG SHALL MATCH ON THE CORRESPONDING
 DRAWINGS. SEE COMMENT 7 REGARDING THE FIXTURE SCHEDULE.
  
 24. SECOND REQUEST: P-05/SANITARY RISER: BATHROOM
 GROUPS PER FBC PL TABLE 710.1, HAVE A FIXTURE UNIT
 VALUE OF 5 PER GROUP. WATER CLOSETS, PRIVATE, 1.6 GPF
 OR LESS HAVE A VALUE OF 3. SHOWERS HAVE A VALUE OF 2.
 PER WPB FBC 107.2.1, PLEASE REVIEW YOUR CALCULATIONS
 AND MODIFY AS IS APPROPRIATE.
  
 25. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE PLANS
 IF THE HOT WATER SYSTEM IS RECIRCULATED OR HEAT TRACED;
 PROVIDE THE TEMPERATURE OF THE HOT WATER.
 TO BE CLEAR, PER FBC PL 607.2, THE DEVELOPED LENGTH OF
 HOT OR TEMPERED WATER PIPING FROM THE SOURCE OF HOT
 WATER TO THE FIXTURE SHALL NOT EXCEED 50 FEET.
 RECIRCULATING SYSTEMS AND HEAT TRACED SYSTEMS ARE
 CONSIDERED TO BE SOURCES OF HOT OR TEMPERED WATER.
 PLEASE SHOW THAT THE HOT OR TEMPERED WATER FROM THE
 SOURCE TO THE FIXTURES DOES NOT EXCEED 50 FEET OR
 PROVIDE MEANS TO COMPLY.
  
 26.NEW COMMENT: FBC ACC 611, PROVIDE THE MEASUREMENTS
 WITHIN THE LAUNDRY ROOMS TO SHOW COMPLIANCE WITH
 ACCESSIBLE REQUIREMENTS INCLUDING CLEAR FLOOR, WHEEL
 CHAIR APPROACH AND REACH REQUIREMENTS.
  
 27. NEW COMMENT: IT APPEARS THAT THE PLUMBING FIXTURE
 SCHEDULE ON P-05 IS FROM THE ORIGINAL CONSTRUCTION AND
 IS NOT APPLICABLE TO THE NEW WORK; SOME PRODUCTS ARE
 DISCONTINUED. PER WPB FBC 107.2.1, PROVIDE AN
 APPLICABLE FIXTURE SCHEDULE; TAG TO MATCH DRAWINGS. SEE
 COMMENT 7 AND 23.
  
 28. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CORRECT
 OCCUPANCY (PER FBC 310.4, R-2) AND THE OCCUPANT LOAD
 FOR THE BUILDING.
  
 29. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A
 PLUMBING FIXTURE SCHEDULE FOR THE BUILDING SHOWING THE
 REQUIRED PLUMBING FIXTURES (SEE FBC PL TABLE 403.1) AND
 THE PROVIDED PLUMBING FIXTURES. THIS DOES NOT APPLY TO
 THE DWELLING UNITS. PLEASE NOTE THAT THE REQUIRED
 DRINKING FOUNTAIN QUANTITY FOR R-2 IS 1 PER 100
 PERSONS. ADDITIONALLY, IN ACCORDANCE WITH FBC PL 410.3
 AND FBC ACC 211.2, A BI-LEVEL DRINKING FOUNTAIN
 CONSTITUTES 2 DRINKING FOUNTAINS.
  
 30. NEW COMMENT: IT APPEARS THAT THE PLUMBING FIXTURE
 SCHEDULE ON P-05 IS FROM THE ORIGINAL CONSTRUCTION AND
 IS NOT APPLICABLE TO THE NEW WORK; SOME PRODUCTS ARE
 DISCONTINUED. PER WPB FBC 107.2.1, PROVIDE AN
 APPLICABLE FIXTURE SCHEDULE; TAG TO MATCH DRAWINGS. SEE
 COMMENT 7 AND 23.
  
 31. NEW COMMENT: PLAN SHEET A-0/APPLICABLE CODES: PER
 WPB FBC 107.2.1, PLEASE ADD 2020 FLORIDA BUILDING CODE,
 EXISTING BUILDING, 7TH EDITION AND PROVIDE THE
 APPLICABLE LEVEL OF OPERATION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 PLEASE PROVIDE A DETAILED RESPONSE LETTER ADDRESING
 EACH ITEM/COMMENT.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928