Plan Review Notes
Plan Review Notes For Permit 22051265
Permit Number 22051265
Review Stop M
Sequence Number 2
Notes
Date Text
2022-07-19 10:30:591) PROVIDE THE CHILLED WATER PIPING DETAILS FOR THE NEW
 FCU'S. FBC 107.2.1
  
 2) PROVIDE THE BATH EXHAUST TIE IN DETAIL TO THE
 EXHISTING EXHAUST SYSTEM. FBC 107.2.1
  
 3) PROVIDE THE DRYER DUCT DETAILS, SIZING MATERIAL AND
 LENGTH OF EXHAUST DUCT ALONG WITH THE TERMINATION
 LOCATION. FMC 504
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE DORM
 ROOMS AND HOW IT WILL BE INTRODUCED. FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
 5) PROVIDE A CONDENSATE DETAIL SHOWING THE PIPE
 MATERIAL, SIZE AND LOCATION OF TERMINATION LOCATION.
 FMC 307
  