| Plan Review Notes For Permit 22051265 |
| Permit Number |
22051265 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-19 10:30:59 | 1) PROVIDE THE CHILLED WATER PIPING DETAILS FOR THE NEW | | | FCU'S. FBC 107.2.1 | | | | | | 2) PROVIDE THE BATH EXHAUST TIE IN DETAIL TO THE | | | EXHISTING EXHAUST SYSTEM. FBC 107.2.1 | | | | | | 3) PROVIDE THE DRYER DUCT DETAILS, SIZING MATERIAL AND | | | LENGTH OF EXHAUST DUCT ALONG WITH THE TERMINATION | | | LOCATION. FMC 504 | | | | | | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE DORM | | | ROOMS AND HOW IT WILL BE INTRODUCED. FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | 5) PROVIDE A CONDENSATE DETAIL SHOWING THE PIPE | | | MATERIAL, SIZE AND LOCATION OF TERMINATION LOCATION. | | | FMC 307 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|