2022-08-11 12:50:39PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING 2ND REVIEW DENIED:
  
 1.) FBC B 310.4, THE OCCUPANCY INDICATED ON THESE PLAN
 SHEETS IS "R-1" BUT THE FLORIDA BUILDING CODE SHOWS
 THIS AS AN "R-2".
  
 2.) FBC R 101.2 & FBC B 101.2, ON PLAN SHEETS A-01&
 A-02, UNDER CONSTRUCTION NOTES, THE INDICATION IS THAT
 THE INFORMATION IS UNDER THE REQUIREMENTS OF THE
 RESIDENTIAL CODE. IT APPEARS THAT THIS PROJECT FALLS
 UNDER THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
 "BUILDING" NOT RESIDENTIAL.
  
 3.) FBC B 107.2.1, THE NEW FLOORING, INCLUDING THE
 UNDERLAYMENT, NEEDS TO COMPLY WITH THE FOLLOWING:
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 4.) FBC A 611, PROVIDE THE MEASUREMENTS WITHIN THE
 LAUNDRY ROOMS TO SHOW COMPLIANCE WITH ACCESSIBLE
 REQUIREMENTS INCLUDING CLEAR FLOOR, WHEEL CHAIR
 APPROACH AND REACH REQUIREMENTS.
  
 5.) FBC B 2403.1, 2403.2, 2403.3, & 2403.4, PROVIDE THE
 REQUIRED DETAILS FOR THE GLASS SHOWER ENCLOSURE AS PER
 THE GLASS & GLAZING SECTIONS OF THE FLORIDA BUILDING
 CODE.
  