| | BUILDING 2ND REVIEW DENIED: |
| | |
| | 1.) FBC B 310.4, THE OCCUPANCY INDICATED ON THESE PLAN |
| | SHEETS IS "R-1" BUT THE FLORIDA BUILDING CODE SHOWS |
| | THIS AS AN "R-2". |
| | |
| | 2.) FBC R 101.2 & FBC B 101.2, ON PLAN SHEETS A-01& |
| | A-02, UNDER CONSTRUCTION NOTES, THE INDICATION IS THAT |
| | THE INFORMATION IS UNDER THE REQUIREMENTS OF THE |
| | RESIDENTIAL CODE. IT APPEARS THAT THIS PROJECT FALLS |
| | UNDER THE REQUIREMENTS OF THE FLORIDA BUILDING CODE |
| | "BUILDING" NOT RESIDENTIAL. |
| | |
| | 3.) FBC B 107.2.1, THE NEW FLOORING, INCLUDING THE |
| | UNDERLAYMENT, NEEDS TO COMPLY WITH THE FOLLOWING: |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 4.) FBC A 611, PROVIDE THE MEASUREMENTS WITHIN THE |
| | LAUNDRY ROOMS TO SHOW COMPLIANCE WITH ACCESSIBLE |
| | REQUIREMENTS INCLUDING CLEAR FLOOR, WHEEL CHAIR |
| | APPROACH AND REACH REQUIREMENTS. |
| | |
| | 5.) FBC B 2403.1, 2403.2, 2403.3, & 2403.4, PROVIDE THE |
| | REQUIRED DETAILS FOR THE GLASS SHOWER ENCLOSURE AS PER |
| | THE GLASS & GLAZING SECTIONS OF THE FLORIDA BUILDING |
| | CODE. |
| | |