Plan Review Notes
Plan Review Notes For Permit 22051265
Permit Number 22051265
Review Stop P
Sequence Number 1
Notes
Date Text
2022-06-07 15:19:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22051265 300 PEMBROKE PL
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PLEASE NOTE FBC ACC 202.4.1, DISPROPORTIONATE COST:
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 ***A) PER WPB FBC 107.2.1, PROVIDE DIMENSIONED PLAN AND
 ELEVATION VIEW OF EXISTING MEN AND WOMEN TOILET ROOMS
 SHOWING COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6 AS
 FOLLOWS:
 *****1) THE WATER CLOSET SHALL BE POSITIONED WITH A
 WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 *****2) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1
 *****3) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 *****4) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 *****5) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 *****6) PER FBC ACC 604.8, TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS.
 *****7) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 *****8) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 *****9) LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER
 FBC ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE
 AS REQUIRED BY FBC ACC 306.2 AND 306.3
 *****10) PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
 *****11) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 *****12) MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS
 TO THE REFLECTING SURFACE OF THE MIRROR.
 *****13) SHOW TURNING SPACE COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2.
 *****14) PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***B) PLEASE NOTE THE DRINKING FOUNTAIN ON PLAN SHEET
 A-01, P-01 AND THE REQUIREMENTS OF FBC ACC 211.1,
 211.2; WHERE DRINKING FOUNTAINS ARE PROVIDED, NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. PER
 WPB FBC 107.2.1, AN ELEVATION AND PLAN DETAIL OF THE
 UPGRADED FIXTURE(S) IS REQUIRED.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***C) PER WPB FBC 107.2.1, PROVIDE ELEVATION AND PLAN
 DETAIL FOR WASHER(S) AND DRYER(S) SHOWING COMPLIANCE
 WITH FBC ACC 214 AND 611. TOP LOADING MACHINES SHALL
 HAVE THE DOOR TO THE LAUNDRY COMPARTMENT LOCATED 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR. FRONT LOADING
 MACHINES SHALL HAVE THE BOTTOM OF THE OPENING TO THE
 LAUNDRY COMPARTMENT LOCATED 15 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR.
 AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED.
 ***D) COST OF SUGGESTED UPGRADES IN EXCESS OF 20% OF
 THE COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA
 SHALL BE DEEMED DISPROPORTIONATE.
  
 2. WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO
 FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC
 ACC 212.3. PER WPB FBC 107.2.1, IDENTIFY ACCESSIBLE
 DORMITORY UNIT(S) AND PROVIDE ELEVATION AND PLAN
 DETAILS FOR NEW SINK SHOWING COMPLIANCE.
  
 3. PER FBC ACC 213.2, WHERE BATHING ROOMS ARE PROVIDED,
 EACH BATHING ROOM SHALL COMPLY WITH 603. PER WPB FBC
 107.2.1, IDENTIFY ACCESSIBLE DORMITORY UNIT(S) AND
 PROVIDE ELEVATION AND PLAN DETAILS FOR NEW BATHING
 ROOM(S) SHOWING COMPLIANCE WITH FBC ACC 603.
 EXCEPTIONS:
 ***1) IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE
 TO COMPLY WITH 603, ALTERING EXISTING TOILET OR BATHING
 ROOMS SHALL NOT BE REQUIRED WHERE A SINGLE UNISEX
 TOILET ROOM OR BATHING ROOM COMPLYING WITH 213.2.1 IS
 PROVIDED AND LOCATED IN THE SAME AREA AND ON THE SAME
 FLOOR AS EXISTING IN ACCESSIBLE TOILET OR BATHING
 ROOMS.
 ***2) WHERE EXCEPTIONS FOR ALTERATIONS TO QUALIFIED
 HISTORIC BUILDINGS OR FACILITIES ARE PERMITTED BY
 202.5, NO FEWER THAN ONE TOILET ROOM FOR EACH SEX
 COMPLYING WITH 603 OR ONE UNISEX TOILET ROOM COMPLYING
 WITH 213.2.1 SHALL BE PROVIDED.
 ***3) WHERE MULTIPLE SINGLE USER PORTABLE TOILET OR
 BATHING UNITS ARE CLUSTERED AT A SINGLE LOCATION, NO
 MORE THAN 5 PERCENT OF THE TOILET UNITS AND BATHING
 UNITS AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH
 603. PORTABLE TOILET UNITS AND BATHING UNITS COMPLYING
 WITH 603 SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL OF ACCESSIBILITY COMPLYING WITH 703.7.2.1.
 ***4) WHERE MULTIPLE SINGLE USER TOILET ROOMS ARE
 CLUSTERED AT A SINGLE LOCATION, NO MORE THAN 50 PERCENT
 OF THE SINGLE USER TOILET ROOMS FOR EACH USE AT EACH
 CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603.
  
 4. PLAN SHEET A-0/APPLICABLE CODES: PER WPB FBC
 107.2.1, PLEASE ADD 2020 FLORIDA PLUMBING CODE 7TH
 EDITION AND 2020 FLORIDA MECHANICAL CODE 7TH EDITION TO
 THE LIST OF APPLICABLE CODES.
  
 5. PLAN SHEET A-0/APPLICABLE CODES: PER FBC 310.4, THE
 OCCUPANCY FOR THIS FACILITY IS R-2 RESIDENTIAL.
  
 6. PLAN SHEET A-01, A-02/CONSTRUCTION NOTE 4: PER WPB
 FBC 107.2.1, 107.3.5.1.3 AND 107.3.5.3, PLUMBING
 FIXTURE SPACING SHALL COMPLY WITH FLORIDA PLUMBING CODE
 2020 7TH EDITION, NOT THE FLORIDA RESIDENTIAL CODE 2020
 7TH EDITION
  
 7. PER WPB FBC 107.2.1, PLEASE IDENTIFY AND TAG ALL NEW
 PLUMBING FIXTURES ON PLUMBING FLOOR PLANS AND
 ISOMETRICS. TAG AND ID SHALL MATCH PLUMBING FIXTURE
 SCHEDULE ON P-05.
  
 8. P-05/PLUMBING NOTES: PER WPB FBC 107.2.1, REVISE THE
 FOLLOWING
 ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE
 AND FITTINGS"
 ***B) NOTE 13 "COPPER WATER PIPING JOINTS TO BE MADE
 WITH LEAD FREE SOLDER"
 ***C) NOTE 14 "VALVES TO BE LEAD FREE"
 ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN
 ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE
 C403.2.10"
 PROVIDE A SPEC THAT COMPLIES
 ***E) NOTE 19 "IN ACCORDANCE WITH FBC PL 604.9, PROVIDE
 WATER HAMMER ARRESTORS AT EACH FIXTURE GROUP CONFORMING
 TO ASSE 1010"
 ***F) ADD NOTE "ALL COMPONENTS IN THE DOMESTIC WATER
 SYSTEM SHALL BE LEAD FREE IN ACCORDANCE WITH FBC PL
 605.2 AND 605.2.1"
  
 8. P-05/PLUMBING FIXTURE SCHEDULE: PER WPB FBC 107.2.1,
 PROVIDE SPEC AND ID/TAG FOR SHOWER. INCLUDE DRAIN,
 SHOWER CONTROL VALVE AND TRIM. PER FBC PL 412.3,
 INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES
 SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE.
  
 9. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER
 WALL/FLOOR/DRAIN AND THRESHOLD DETAIL
 ***A) DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL
 421.5.2 AS FOLLOWS
 LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED
 BACKING
 LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT
 LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAIN
 LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET
 AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT
 BETWEEN THE LINER AND THE OUTLET
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 ***B) LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING
 WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED.
 ***C) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 ABOVE THE DRAIN OF THE SHOWER.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 11. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL
 ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 12. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 13. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING ?HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT.
  
 14. P-07/RISER DIAGRAM: PER FBC PL 606.1(6) PROVIDE A
 FULL OPEN VALVE TO EACH HOT AND COLD WATER SUPPLY TO
 EACH NEW UNIT. THE LAVATORIES SHALL BE INSTALLED
 DOWNSTREAM OF SAID VALVES.
  
 15. P-07/RISER DIAGRAM: PER WPB FBC 107.2.1, IDENTIFY
 THE WATER HAMMER ARRESTORS (WHA) ON THE WATER RISER
 DIAGRAMS.
  
 16. PER FBC PL 604.1, THE DESIGN OF THE WATER
 DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED
 ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE
 PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER
 DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING
 SYSTEM IS AN APPROVED METHOD.
  
 17. P-01/EXISTING FLOOR DRAIN: PER WPB FBC 107.2.1,
 CONFIRM THAT THE EXISTING FLOOR DRAIN IN THE NEW
 BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE PLAN HOW
 IT IS PROVIDED. IF NOT, THEN PER FBC PL 1002.4.1,
 PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE WITH ONE OF
 THE METHODS IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
 ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL.
  
 18. P-05/SANITARY RISER DIAGRAM: PER FBC PL 909.1, EACH
 FIXTURE TRAP SHALL HAVE A PROTECTING VENT LOCATED SO
 THAT THE SLOPE AND THE DEVELOPED LENGTH IN THE FIXTURE
 DRAIN FROM THE TRAP WEIR TO THE VENT FITTING ARE WITHIN
 THE REQUIREMENTS SET FORTH IN TABLE 909.1. THE WATER
 CLOSETS AND SHOWERS ON THE FIRST, SECOND AND THIRD
 FLOORS DO NOT COMPLY. PER WPB FBC 107.2.1, VENT EACH OF
 THE WATER CLOSETS AND SHOWERS IN ACCORDANCE WITH ONE OF
 THE PRESCRIBED METHODS IN CHAPTER 9. TYPICALLY, THE
 PROVISIONS OF FBC PL SECTION 912, WOULD BE A SUITABLE
 METHOD FOR THIS APPLICATION.
  
 19. P-05/SANITARY RISER SERVICING ONLY FLOORS TWO
 THROUGH 4: PER FBC PL 912.1.1, THE SHOWER DRAIN ON THE
 FOURTH FLOOR SHALL CONNECT TO THE STACK AT OR ABOVE THE
 WATER CLOSET ELEVATION. PLEASE NOTE ALSO THAT ANY TIME
 A WATER CLOSET AND OTHER BATHROOM GROUP FIXTURES ARE
 CONNECTED TO ANY VERTICAL WET VENT, THE OTHER FIXTURES
 SHALL CONNECT AT OR ABOVE THE ELEVATION WITH THE WATER
 CLOSET AS NOTED IN 912.1.1.
  
 20. P-05/SANITARY RISER GROUND FLOOR: THE BRANCH
 BETWEEN THE FLOOR DRAIN AND THE CONNECTION RECEIVING
 THE BATHROOM GROUPS DISCHARGE IS INCORRECTLY TAGGED
 VTR. PER WPB FBC 107.2.1, PLEASE CORRECT.
  
 21. P-05/SANITARY RISER WITH GROUND FLOOR BATHROOM:
 WATER CLOSET FIXTURE DRAIN SHALL BE 3 INCH MINIMUM SIZE
 PER FBC PL 704.2, TABLE 709.1(D) AND 710.1(2)-A
  
 22. PER WPB FBC 107.2.1, ID/TAG THE SANITARY AND WATER
 RISERS ON BOTH RISER DIAGRAMS AND FLOOR PLANS. ID/TAG
 SHALL MATCH ON THE CORRESPONDING DRAWINGS.
  
 23. P-05/SANITARY RISER: BATHROOM GROUPS PER FBC PL
 TABLE 710.1, HAVE A FIXTURE UNIT VALUE OF 5 PER GROUP.
 WATER CLOSETS, PRIVATE, 1.6 GPF OR LESS HAVE A VALUE OF
 3. SHOWERS HAVE A VALUE OF 2. PER WPB FBC 107.2.1,
 PLEASE REVIEW YOUR CALCULATIONS AND MODIFY AS IS
 APPROPRIATE.
  
 24. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE PLANS
 IF THE HOT WATER SYSTEM IS RECIRCULATED OR HEAT TRACED;
 PROVIDE THE TEMPERATURE OF THE HOT WATER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS