| 2022-06-07 15:19:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22051265 300 PEMBROKE PL |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PLEASE NOTE FBC ACC 202.4.1, DISPROPORTIONATE COST: |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | ***A) PER WPB FBC 107.2.1, PROVIDE DIMENSIONED PLAN AND |
| | ELEVATION VIEW OF EXISTING MEN AND WOMEN TOILET ROOMS |
| | SHOWING COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6 AS |
| | FOLLOWS: |
| | *****1) THE WATER CLOSET SHALL BE POSITIONED WITH A |
| | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION PER FBC ACC 604.2 |
| | *****2) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER |
| | CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED |
| | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL |
| | PER FBC ACC 604.3.1 AND 604.8.1.1 |
| | *****3) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | *****4) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | *****5) FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| | *****6) PER FBC ACC 604.8, TOILET PAPER DISPENSERS |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE |
| | LOCATED BEHIND GRAB BARS. |
| | *****7) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE |
| | FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 |
| | INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE |
| | SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED |
| | POSITION PER FBC ACC 604.4. |
| | *****8) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED |
| | IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE |
| | TOP (NOT THE CENTER) OF THE GRIPPING SURFACE. |
| | *****9) LAVATORIES AND SINKS SHALL BE INSTALLED WITH |
| | THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE |
| | 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER |
| | FBC ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE |
| | AS REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | *****10) PER FBC 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | *****11) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | *****12) MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS |
| | TO THE REFLECTING SURFACE OF THE MIRROR. |
| | *****13) SHOW TURNING SPACE COMPLYING WITH FBC ACC |
| | 304.3.1 OR 304.3.2. |
| | *****14) PER FBC 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***B) PLEASE NOTE THE DRINKING FOUNTAIN ON PLAN SHEET |
| | A-01, P-01 AND THE REQUIREMENTS OF FBC ACC 211.1, |
| | 211.2; WHERE DRINKING FOUNTAINS ARE PROVIDED, NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. PER |
| | WPB FBC 107.2.1, AN ELEVATION AND PLAN DETAIL OF THE |
| | UPGRADED FIXTURE(S) IS REQUIRED. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***C) PER WPB FBC 107.2.1, PROVIDE ELEVATION AND PLAN |
| | DETAIL FOR WASHER(S) AND DRYER(S) SHOWING COMPLIANCE |
| | WITH FBC ACC 214 AND 611. TOP LOADING MACHINES SHALL |
| | HAVE THE DOOR TO THE LAUNDRY COMPARTMENT LOCATED 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. FRONT LOADING |
| | MACHINES SHALL HAVE THE BOTTOM OF THE OPENING TO THE |
| | LAUNDRY COMPARTMENT LOCATED 15 INCHES MINIMUM AND 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***D) COST OF SUGGESTED UPGRADES IN EXCESS OF 20% OF |
| | THE COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA |
| | SHALL BE DEEMED DISPROPORTIONATE. |
| | |
| | 2. WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO |
| | FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 PER FBC |
| | ACC 212.3. PER WPB FBC 107.2.1, IDENTIFY ACCESSIBLE |
| | DORMITORY UNIT(S) AND PROVIDE ELEVATION AND PLAN |
| | DETAILS FOR NEW SINK SHOWING COMPLIANCE. |
| | |
| | 3. PER FBC ACC 213.2, WHERE BATHING ROOMS ARE PROVIDED, |
| | EACH BATHING ROOM SHALL COMPLY WITH 603. PER WPB FBC |
| | 107.2.1, IDENTIFY ACCESSIBLE DORMITORY UNIT(S) AND |
| | PROVIDE ELEVATION AND PLAN DETAILS FOR NEW BATHING |
| | ROOM(S) SHOWING COMPLIANCE WITH FBC ACC 603. |
| | EXCEPTIONS: |
| | ***1) IN ALTERATIONS WHERE IT IS TECHNICALLY INFEASIBLE |
| | TO COMPLY WITH 603, ALTERING EXISTING TOILET OR BATHING |
| | ROOMS SHALL NOT BE REQUIRED WHERE A SINGLE UNISEX |
| | TOILET ROOM OR BATHING ROOM COMPLYING WITH 213.2.1 IS |
| | PROVIDED AND LOCATED IN THE SAME AREA AND ON THE SAME |
| | FLOOR AS EXISTING IN ACCESSIBLE TOILET OR BATHING |
| | ROOMS. |
| | ***2) WHERE EXCEPTIONS FOR ALTERATIONS TO QUALIFIED |
| | HISTORIC BUILDINGS OR FACILITIES ARE PERMITTED BY |
| | 202.5, NO FEWER THAN ONE TOILET ROOM FOR EACH SEX |
| | COMPLYING WITH 603 OR ONE UNISEX TOILET ROOM COMPLYING |
| | WITH 213.2.1 SHALL BE PROVIDED. |
| | ***3) WHERE MULTIPLE SINGLE USER PORTABLE TOILET OR |
| | BATHING UNITS ARE CLUSTERED AT A SINGLE LOCATION, NO |
| | MORE THAN 5 PERCENT OF THE TOILET UNITS AND BATHING |
| | UNITS AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH |
| | 603. PORTABLE TOILET UNITS AND BATHING UNITS COMPLYING |
| | WITH 603 SHALL BE IDENTIFIED BY THE INTERNATIONAL |
| | SYMBOL OF ACCESSIBILITY COMPLYING WITH 703.7.2.1. |
| | ***4) WHERE MULTIPLE SINGLE USER TOILET ROOMS ARE |
| | CLUSTERED AT A SINGLE LOCATION, NO MORE THAN 50 PERCENT |
| | OF THE SINGLE USER TOILET ROOMS FOR EACH USE AT EACH |
| | CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. |
| | |
| | 4. PLAN SHEET A-0/APPLICABLE CODES: PER WPB FBC |
| | 107.2.1, PLEASE ADD 2020 FLORIDA PLUMBING CODE 7TH |
| | EDITION AND 2020 FLORIDA MECHANICAL CODE 7TH EDITION TO |
| | THE LIST OF APPLICABLE CODES. |
| | |
| | 5. PLAN SHEET A-0/APPLICABLE CODES: PER FBC 310.4, THE |
| | OCCUPANCY FOR THIS FACILITY IS R-2 RESIDENTIAL. |
| | |
| | 6. PLAN SHEET A-01, A-02/CONSTRUCTION NOTE 4: PER WPB |
| | FBC 107.2.1, 107.3.5.1.3 AND 107.3.5.3, PLUMBING |
| | FIXTURE SPACING SHALL COMPLY WITH FLORIDA PLUMBING CODE |
| | 2020 7TH EDITION, NOT THE FLORIDA RESIDENTIAL CODE 2020 |
| | 7TH EDITION |
| | |
| | 7. PER WPB FBC 107.2.1, PLEASE IDENTIFY AND TAG ALL NEW |
| | PLUMBING FIXTURES ON PLUMBING FLOOR PLANS AND |
| | ISOMETRICS. TAG AND ID SHALL MATCH PLUMBING FIXTURE |
| | SCHEDULE ON P-05. |
| | |
| | 8. P-05/PLUMBING NOTES: PER WPB FBC 107.2.1, REVISE THE |
| | FOLLOWING |
| | ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE |
| | AND FITTINGS" |
| | ***B) NOTE 13 "COPPER WATER PIPING JOINTS TO BE MADE |
| | WITH LEAD FREE SOLDER" |
| | ***C) NOTE 14 "VALVES TO BE LEAD FREE" |
| | ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN |
| | ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE |
| | C403.2.10" |
| | PROVIDE A SPEC THAT COMPLIES |
| | ***E) NOTE 19 "IN ACCORDANCE WITH FBC PL 604.9, PROVIDE |
| | WATER HAMMER ARRESTORS AT EACH FIXTURE GROUP CONFORMING |
| | TO ASSE 1010" |
| | ***F) ADD NOTE "ALL COMPONENTS IN THE DOMESTIC WATER |
| | SYSTEM SHALL BE LEAD FREE IN ACCORDANCE WITH FBC PL |
| | 605.2 AND 605.2.1" |
| | |
| | 8. P-05/PLUMBING FIXTURE SCHEDULE: PER WPB FBC 107.2.1, |
| | PROVIDE SPEC AND ID/TAG FOR SHOWER. INCLUDE DRAIN, |
| | SHOWER CONTROL VALVE AND TRIM. PER FBC PL 412.3, |
| | INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES |
| | SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| | B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| | INSTALLED AT THE POINT OF USE. |
| | |
| | 9. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER |
| | WALL/FLOOR/DRAIN AND THRESHOLD DETAIL |
| | ***A) DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL |
| | 421.5.2 AS FOLLOWS |
| | LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| | INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| | LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| | BACKING |
| | LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| | LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAIN |
| | LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| | AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| | BETWEEN THE LINER AND THE OUTLET |
| | FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| | LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| | SOUND BASE. |
| | ***B) LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING |
| | WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| | 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| | 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED |
| | POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| | ***C) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS |
| | SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| | NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | ABOVE THE DRAIN OF THE SHOWER. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 11. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL |
| | ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| | WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING |
| | WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| | |
| | 13. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL |
| | 704.1, PROVIDE NOTE STATING ?HORIZONTAL DRAINAGE PIPING |
| | LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF |
| | 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE |
| | A MINIMUM SLOPE OF 1/8 INCH PER FOOT. |
| | |
| | 14. P-07/RISER DIAGRAM: PER FBC PL 606.1(6) PROVIDE A |
| | FULL OPEN VALVE TO EACH HOT AND COLD WATER SUPPLY TO |
| | EACH NEW UNIT. THE LAVATORIES SHALL BE INSTALLED |
| | DOWNSTREAM OF SAID VALVES. |
| | |
| | 15. P-07/RISER DIAGRAM: PER WPB FBC 107.2.1, IDENTIFY |
| | THE WATER HAMMER ARRESTORS (WHA) ON THE WATER RISER |
| | DIAGRAMS. |
| | |
| | 16. PER FBC PL 604.1, THE DESIGN OF THE WATER |
| | DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED |
| | ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE |
| | PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER |
| | DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING |
| | SYSTEM IS AN APPROVED METHOD. |
| | |
| | 17. P-01/EXISTING FLOOR DRAIN: PER WPB FBC 107.2.1, |
| | CONFIRM THAT THE EXISTING FLOOR DRAIN IN THE NEW |
| | BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE PLAN HOW |
| | IT IS PROVIDED. IF NOT, THEN PER FBC PL 1002.4.1, |
| | PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE WITH ONE OF |
| | THE METHODS IN SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4. |
| | ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL. |
| | |
| | 18. P-05/SANITARY RISER DIAGRAM: PER FBC PL 909.1, EACH |
| | FIXTURE TRAP SHALL HAVE A PROTECTING VENT LOCATED SO |
| | THAT THE SLOPE AND THE DEVELOPED LENGTH IN THE FIXTURE |
| | DRAIN FROM THE TRAP WEIR TO THE VENT FITTING ARE WITHIN |
| | THE REQUIREMENTS SET FORTH IN TABLE 909.1. THE WATER |
| | CLOSETS AND SHOWERS ON THE FIRST, SECOND AND THIRD |
| | FLOORS DO NOT COMPLY. PER WPB FBC 107.2.1, VENT EACH OF |
| | THE WATER CLOSETS AND SHOWERS IN ACCORDANCE WITH ONE OF |
| | THE PRESCRIBED METHODS IN CHAPTER 9. TYPICALLY, THE |
| | PROVISIONS OF FBC PL SECTION 912, WOULD BE A SUITABLE |
| | METHOD FOR THIS APPLICATION. |
| | |
| | 19. P-05/SANITARY RISER SERVICING ONLY FLOORS TWO |
| | THROUGH 4: PER FBC PL 912.1.1, THE SHOWER DRAIN ON THE |
| | FOURTH FLOOR SHALL CONNECT TO THE STACK AT OR ABOVE THE |
| | WATER CLOSET ELEVATION. PLEASE NOTE ALSO THAT ANY TIME |
| | A WATER CLOSET AND OTHER BATHROOM GROUP FIXTURES ARE |
| | CONNECTED TO ANY VERTICAL WET VENT, THE OTHER FIXTURES |
| | SHALL CONNECT AT OR ABOVE THE ELEVATION WITH THE WATER |
| | CLOSET AS NOTED IN 912.1.1. |
| | |
| | 20. P-05/SANITARY RISER GROUND FLOOR: THE BRANCH |
| | BETWEEN THE FLOOR DRAIN AND THE CONNECTION RECEIVING |
| | THE BATHROOM GROUPS DISCHARGE IS INCORRECTLY TAGGED |
| | VTR. PER WPB FBC 107.2.1, PLEASE CORRECT. |
| | |
| | 21. P-05/SANITARY RISER WITH GROUND FLOOR BATHROOM: |
| | WATER CLOSET FIXTURE DRAIN SHALL BE 3 INCH MINIMUM SIZE |
| | PER FBC PL 704.2, TABLE 709.1(D) AND 710.1(2)-A |
| | |
| | 22. PER WPB FBC 107.2.1, ID/TAG THE SANITARY AND WATER |
| | RISERS ON BOTH RISER DIAGRAMS AND FLOOR PLANS. ID/TAG |
| | SHALL MATCH ON THE CORRESPONDING DRAWINGS. |
| | |
| | 23. P-05/SANITARY RISER: BATHROOM GROUPS PER FBC PL |
| | TABLE 710.1, HAVE A FIXTURE UNIT VALUE OF 5 PER GROUP. |
| | WATER CLOSETS, PRIVATE, 1.6 GPF OR LESS HAVE A VALUE OF |
| | 3. SHOWERS HAVE A VALUE OF 2. PER WPB FBC 107.2.1, |
| | PLEASE REVIEW YOUR CALCULATIONS AND MODIFY AS IS |
| | APPROPRIATE. |
| | |
| | 24. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE PLANS |
| | IF THE HOT WATER SYSTEM IS RECIRCULATED OR HEAT TRACED; |
| | PROVIDE THE TEMPERATURE OF THE HOT WATER. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |