Plan Review Notes
Plan Review Notes For Permit 22051250
Permit Number 22051250
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-31 11:17:45ELEVATION CERTIFICATES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING GA-1A SHOWS INTERIOR WALLS TO HAVE FIRE
 RATED FLOOD VENTS - PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE FIRE RATED SMART VENTS - LIST THE FIRE RATED
 SMART VENT MODEL NUMBER ON THE ELEVATION CERTIFICATE.
  
 2) A9(D) SHOULD BE MARKED "YES" - - - FROM THE EC
 INSTRUCTIONS ITEMS A9.B?D. INDICATE IN ITEM A9.D
 WHETHER THE FLOOD OPENINGS ARE ENGINEERED. IF
 APPLICABLE, ATTACH A COPY OF THE INDIVIDUAL ENGINEERED
 FLOOD OPENINGS CERTIFICATION OR AN EVALUATION REPORT
 ISSUED BY THE INTERNATIONAL CODE COUNCIL EVALUATION
 SERVICE (ICC ES),
  
 3) SECTION "D" "CHECK HERE IF ATTACHMENTS" SHOULD BE
 CHECKED - - - - FROM THE EC INSTRUCTIONS ITEMS A9.B?D.
 IF APPLICABLE, ATTACH A COPY OF THE INDIVIDUAL
 ENGINEERED FLOOD OPENINGS CERTIFICATION OR AN
 EVALUATION REPORT ISSUED BY THE INTERNATIONAL CODE
 COUNCIL EVALUATION SERVICE (ICC ES),