2023-06-26 19:09:27RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
 3- OK. WINDOW AND DOOR HURRICANE SHUTTERS UNDER PERMIT
 #23040271.
  
  
 PREVIOUS COMMENT:
 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER
 SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION
 (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF
 THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE
 PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY
 WILL BE APPLIED IF THAT IS THE INTENTION.
 PREVIOUS RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
 CONTRACTOR'S RESPONSE LETTER STATES "SEE REVISED SHEET
 S1.0.". SHEET S1.0 WAS NOT REVISED. SAME SPECIFICATIONS
 ARE SHOWN. SINCE THE ATTIC IS NOT VENTED, IT LOOKS LIKE
 FOAM INSULATION WILL BE REQUIRED. REVISE INFORMATION ON
 SHEET S1.0. SPECIFY FOAM INSULATION AND R-VALUE.
 ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY
 OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS).
  
 NEW RESPONSE:
 DETAIL F.2 ON SHEET S1.0 WAS REVISED SHOWING R-20
 ICYNENE SPRAY FOAM INSULATION BUT THE ENERGY
 CALCULATIONS WERE NOT REVISED:
 A) REVISE CEILING INSULATION R-VALUE TO MATCH REVISED
 PLANS.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)REVISE CONCRETE BLOCK INSULATION R-VALUE TO MATCH
 REVISED PLANS.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) REVISE ITEM #1 ON PAGE ONE OF ENERGY CALCULATIONS.
 THIS IS NOT AN ADDITION. THIS IS AN ALTERATION TO
 EXISTING BUILDING (GARAGE).
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D)ICYNENE EVALUATION REPORT ESR-1826 SUBMITTED IS
 EXPIRED. IT HAD TO BE RENEWED ON 02/2018. SEE RIGHT TOP
 CORNER BELOW ESR-1826. PROVIDE CURRENT EVALUATION
 REPORT.
 SEC. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENTS BASED ON NEW INFORMATION SUBMITTED.
 7- DRAWING D1.0 SHOWS A NEW DECORATIVE GATE ELEVATION.
 NEED TO PROVIDE THE FOLLOWING FOR REVIEW:
 A)PROVIDE COMPLETE SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR THE CONSTRUCTION AND INSTALLATION OF
 THIS DOOR.
 NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION
 THE INSTALLATION OF HURRICANE STORM PANELS (SEE
 SEPARATE PERMIT) TO AVOID CONFLICTS/DELAYS.
 FAC 61G20.3001. SEC. R301.2.1 FBC-RESIDENTIAL. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 B) SHOW LOCATION OF THE PROPOSED DOOR.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- UPDATE VALUATION TO INCLUDE THE ADDTIONAL DOOR .
 INCLUDE THE LABOR AND MATERIALS AND ENGINEERING. SEC.
 109.3 CITY AMENDMENTS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 MASONRY WALL FLASHING AT ALL NEW EXTERIOR OPENINGS.
 SEC. R703.4 FBC-RESIDENTIAL.
 SHOW LOCATION OF PROPOSED DOOR.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE EXTERIOR DOOR AND WINDOW STRUCTURAL BUCK
 DETAIL SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 11- DOOR AND WINDOW WIND PRESSURES SPECIFIED UNDER WIND
 PRESSURE LOAD ON SHEET D1.0 ARE TOO LOW FOR EXPOSURE C.
 REVISE AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: WINDOW IS LOCATED IN END ZONE #5 NOT #4. SEE NOTE
 "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 12- 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED
 ON SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE
 LEAF. VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR
 REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING
 SPECIFIED ON THE STRUCTURAL DRAWING.
 SEC. 107.2.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved