Plan Review Notes
Plan Review Notes For Permit 22051247
Permit Number 22051247
Review Stop B
Sequence Number 4
Notes
Date Text
2023-03-15 17:17:20RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
  
 PREVIOUS COMMENT:
 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE
 INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A
 CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION.
  
 RESPONSE:
 CONTRACTOR'S RESPONSE LETTER STATES "THERE WILL BE A
 SEPARATE PERMIT PULLED BY THE COMPANY THAT'LL BE
 INSTALLING HURRICANE SHUTTERS". PERMIT APPLICATION FOR
 SHUTTERS HAS NOT BEEN SUBMITTED YET. THIS ITEM WILL BE
 APPROVED WHEN CONTRACTOR APPLIES FOR SHUTTERS PERMIT
 AND PROVIDES COMPLETE INFORMATION FOR REVIEW.
  
  
 PREVIOUS COMMENT:
 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER
 SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION
 (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF
 THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE
 PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY
 WILL BE APPLIED IF THAT IS THE INTENTION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CONTRACTOR'S RESPONSE
 LETTER STATES "SEE REVISED SHEET S1.0.". SHEET S1.0 WAS
 NOT REVISED. SAME SPECIFICATIONS ARE SHOWN. SINCE THE
 ATTIC IS NOT VENTED, IT LOOKS LIKE FOAM INSULATION WILL
 BE REQUIRED. REVISE INFORMATION ON SHEET S1.0. SPECIFY
 FOAM INSULATION AND R-VALUE.
 ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY
 OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS).
  
  
  
 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND
 SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
  
  
 NOTE TO CONTRACTOR:
 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED ON
 SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE LEAF.
 VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR
 REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING
 SPECIFIED ON THE STRUCTURAL DRAWING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  