| Plan Review Notes For Permit 22051247 |
| Permit Number |
22051247 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-02-22 15:38:25 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC EC R 103.1.1.2, THE ENERGY CALCULATIONS ARE | | | MISSING THE SIGNATURES BY THE OWNER/OWNER'S | | | REPRESENTATIVE. | | | | | | 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE | | | INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A | | | CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION. | | | | | | 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER | | | SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION | | | (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF | | | THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE | | | PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY | | | WILL BE APPLIED IF THAT IS THE INTENTION. | | | | | | 6.B.) FBC B 107.2.1, FOR THE WALL INSULATION (R-11 | | | PAPER BACK) WITHIN THE WOOD FRAMED WALL DETAIL F.1 ON | | | PLAN SHEET S1.0, THIS DETAIL STILL INDICATES 2"X 4" | | | WALL FRAMING. PLEASE CHANGE THE DETAIL TO INDICATE THE | | | WALL FRAMING SIZE THAT WILL ACCOMODATE THE R-11 PAPER | | | BACK INSULATION THICKNESS REQUIREMENT. |
|