| 2022-10-06 17:07:20 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22051247 |
| | 522 28TH ST |
| | |
| | NOTE: |
| | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. |
| | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. |
| | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN |
| | CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING |
| | EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE |
| | COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS, |
| | WINDOWS). |
| | |
| | RESPONSE: |
| | A)CLARIFY WHERE ARE THE WINDOW AND DOOR WIND PRESSURE |
| | LOADS TAKEN FROM? THEY ARE TOO LOW FOR A BUILDING IN |
| | EXPOSURE "C". |
| | SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | |
| | B)WINDOW AND DOOR SCHEDULE SPECIFY D.P.R. PSI. WHAT IS |
| | THIS?. |
| | NOTE: DESIGN PRESSURES ARE GIVEN IN POUNDS PER SQUARE |
| | FEET NOT POUNDS PER SQUARE INCH. REVISE /CLARIFY. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED |
| | DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO |
| | PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32 |
| | INCHES. SEC. R311.2 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | 5'-0" DOUBLE HUNG DOESN'T COMPLY. NEED DOOR THAT |
| | PROVIDES AT LEAST 32" CLEAR WIDTH OPENING WHEN ONE LEAF |
| | IS OPEN. |
| | |
| | ORIGINAL COMMENT: |
| | 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR. |
| | SEE ITEM #2 ABOVE. |
| | SEC. 61G20.3.001 F.A.C. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE |
| | WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM |
| | THE GARAGE TO THE HABITABLE ROOM. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING |
| | THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS |
| | AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY |
| | SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | STRUCTURAL DRAWING S1.0: |
| | A)DETAIL F.2 SHOWS R-30 PAPER BACK ROOF INSULATION. |
| | DETAIL IS NOT CLEAR HOW THE INSULATION IS INSTALLED. |
| | R-30 PAPER BACK INSULATION IS +/- 9-1/2" THICK. THIS |
| | INSULATION WILL COMPLETELY FILL THE 2X10 EXISTING ROOF |
| | JOIST. |
| | THEREFORE, THE DETAIL IS INCORRECT. DESIGNER OF RECORD |
| | TO SPECIFY IF THE ATTIC IS VENTED OR UNVENTED. IF |
| | VENTED, THEN THE INSULATION DOESN'T PROVIDE CROSS |
| | VENTILATION. THEREFORE IT DOESN'T WORK. IF NOT VENTED, |
| | THEN PROVIDE COMPLETE DETAIL SPECIFICATIONS FOR TYPE OF |
| | INSULATION SHOWING COMPLIANCE WITH SEC. R806.5 |
| | FBC-RESIDENTIAL. |
| | NOTE: IF SPECIFYING SPRAY FOAM INSULATION, THEN PROVIDE |
| | ICC EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY |
| | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | |
| | B)DETAIL F.1: R19 PAPER BACK INSULATION IS +/- 6-1/4" |
| | THICK. THEREFORE IT DOESN'T FIT ON A 2X4 WALL. REVISE |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C)EXTERIOR WALL SPECIFICATIONS ON DETAIL F.2 DON'T |
| | SPECIFY INSULATION R-VALUE. ALSO, PROVIDE ICC |
| | EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY |
| | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | |
| | ORIGINAL COMMENT: |
| | 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING |
| | COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL. |
| | SPECIFY STRUCTURAL BUCK SIZE AND FASTENING. |
| | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT BASED ON NEW INFORMATION SUBMITTED: |
| | 8- STRUCTURAL DETAILS ON SHEET S1.0 ARE NOT CLEAR AND |
| | ARE INCOMPLETE. SPECIFICATIONS FOR VERTICAL |
| | REINFORCEMENT AT THE END OF EACH OPENING IS NOT CLEAR. |
| | CLARIFY WHY DON'T SPECIFYING CONTINUOUS REINFORCEMENT |
| | FROM TOP TO BOTTOM. OVERLAP OF REBARS IS NOT SPECIFIED. |
| | THERE ARE NO SPECS SHOWING HOW THE END COLUMNS ARE |
| | FILLED. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 9- NEW HABITABLE ROOM NEEDS TO HAVE HEATING AS REQUIRED |
| | BY SEC. R303.10 FBC-RESIDENTIAL. |
| | |
| | 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND |
| | SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |