Plan Review Notes
Plan Review Notes For Permit 22051247
Permit Number 22051247
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-06 17:07:20RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN
 CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING
 EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE
 COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS,
 WINDOWS).
  
 RESPONSE:
 A)CLARIFY WHERE ARE THE WINDOW AND DOOR WIND PRESSURE
 LOADS TAKEN FROM? THEY ARE TOO LOW FOR A BUILDING IN
 EXPOSURE "C".
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
  
 B)WINDOW AND DOOR SCHEDULE SPECIFY D.P.R. PSI. WHAT IS
 THIS?.
 NOTE: DESIGN PRESSURES ARE GIVEN IN POUNDS PER SQUARE
 FEET NOT POUNDS PER SQUARE INCH. REVISE /CLARIFY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED
 DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO
 PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32
 INCHES. SEC. R311.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 5'-0" DOUBLE HUNG DOESN'T COMPLY. NEED DOOR THAT
 PROVIDES AT LEAST 32" CLEAR WIDTH OPENING WHEN ONE LEAF
 IS OPEN.
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR.
 SEE ITEM #2 ABOVE.
 SEC. 61G20.3.001 F.A.C.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE
 WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM
 THE GARAGE TO THE HABITABLE ROOM.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS
 AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STRUCTURAL DRAWING S1.0:
 A)DETAIL F.2 SHOWS R-30 PAPER BACK ROOF INSULATION.
 DETAIL IS NOT CLEAR HOW THE INSULATION IS INSTALLED.
 R-30 PAPER BACK INSULATION IS +/- 9-1/2" THICK. THIS
 INSULATION WILL COMPLETELY FILL THE 2X10 EXISTING ROOF
 JOIST.
 THEREFORE, THE DETAIL IS INCORRECT. DESIGNER OF RECORD
 TO SPECIFY IF THE ATTIC IS VENTED OR UNVENTED. IF
 VENTED, THEN THE INSULATION DOESN'T PROVIDE CROSS
 VENTILATION. THEREFORE IT DOESN'T WORK. IF NOT VENTED,
 THEN PROVIDE COMPLETE DETAIL SPECIFICATIONS FOR TYPE OF
 INSULATION SHOWING COMPLIANCE WITH SEC. R806.5
 FBC-RESIDENTIAL.
 NOTE: IF SPECIFYING SPRAY FOAM INSULATION, THEN PROVIDE
 ICC EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
  
 B)DETAIL F.1: R19 PAPER BACK INSULATION IS +/- 6-1/4"
 THICK. THEREFORE IT DOESN'T FIT ON A 2X4 WALL. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 C)EXTERIOR WALL SPECIFICATIONS ON DETAIL F.2 DON'T
 SPECIFY INSULATION R-VALUE. ALSO, PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT BASED ON NEW INFORMATION SUBMITTED:
 8- STRUCTURAL DETAILS ON SHEET S1.0 ARE NOT CLEAR AND
 ARE INCOMPLETE. SPECIFICATIONS FOR VERTICAL
 REINFORCEMENT AT THE END OF EACH OPENING IS NOT CLEAR.
 CLARIFY WHY DON'T SPECIFYING CONTINUOUS REINFORCEMENT
 FROM TOP TO BOTTOM. OVERLAP OF REBARS IS NOT SPECIFIED.
 THERE ARE NO SPECS SHOWING HOW THE END COLUMNS ARE
 FILLED.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 9- NEW HABITABLE ROOM NEEDS TO HAVE HEATING AS REQUIRED
 BY SEC. R303.10 FBC-RESIDENTIAL.
  
 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND
 SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  