| 2022-06-27 12:32:20 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22051238 |
| | 6/27/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FHDA- FAIR HOUSING DESIGN ACT MANUAL |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) BASED ON THE SUBMITTED PHOTO OF THE SHOWER AND THE |
| | BATHROOM, THE LAYOUT PLAN NEEDS TO BE MODIFIED TO SHOW |
| | THE FULL SCOPE OF WORK WHICH INCLUDES DEMOLITION AND |
| | REMODELING TO ENLARGE THE SHOWER IN THE BATHROOM. |
| | PLEASE PROVIDE A DIMENSIONED PLAN THAT SHOWS THE |
| | EXISTING BATH AND THE REMODELED BATH- SEC. 107.2.1 WPB. |
| | |
| | 2) FAIR HOUSING COMPLIANCE: SHOW THE REQUIRED |
| | 30X48-INCH CLEAR FLOOR SPACE DIAGRAM POSITIONED FOR A |
| | PARALLEL APPROACH TO THE SHOWER- PAGES 7.56- 7.59 FHDA. |
| | PLEASE NOTE THAT NO FIXTURES ARE ALLOWED TO OVERLAP THE |
| | CLEAR FLOOR SPACES REQUIRED FOR THE SHOWER. |
| | |
| | 3) FAIR HOUSING COMPLIANCE: REFER TO PAGES 6.12- 6.13 |
| | OF THE FHDA MANUAL AND PROVIDE AN ELEVATION DETAIL |
| | SHOWING THE SHOWER CONTROLS LOCATION, AND THE GRAB BAR |
| | REINFORCEMENT DETAILS. SHOW THE LENGTHS, WIDTHS AND |
| | HEIGHTS AND THE TYPE OF REINFORCEMENT MATERIAL TO BE |
| | USED. PLEASE SEE SECTION 603.1 FOR ALLOWABLE MATERIALS |
| | IN NON-COMBUSTIBLE BUILDINGS. |
| | |
| | PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| | GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| | DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| | A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| | ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| | THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| | REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| | REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| | PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| | COPY OF THE FAIR HOUSING AFFIDAVIT. |
| | |
| | 4) IT APPEARS THE SHOWER DRAIN MAY HAVE TO BE |
| | RELOCATRED. RELOCATING THE SHOWER DRAIN OUTLET MAY |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SEC. 107.2.1 WPB. |
| | |
| | 5) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SEC. 315.1 |
| | FBC P AND SEC. 714.4.1.2 FBC B. |
| | |
| | 6) THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER SHALL |
| | BE ON THE DRAWINGS- SEC.107.2.1 WPB, AND FL. STATUTES |
| | 471.003(2)(H) & 471.025 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |