| Plan Review Notes For Permit 22051233 |
| Permit Number |
22051233 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-15 13:00:31 | PLEASE SEE PREVIOUS REVIEW COMMENT BELOW: | | | | | | 1ST REVIEW FMC | | | PERMIT: 22051233 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) I CANNOT COMPLETE A REVIEW AT THIS TIME. REMOVE THE | | | LAYERS FROM SHEETS AFS-7, AFS-8 AND BOTH AFS-9 AS THEY | | | MAKE IT IMPOSSIBLE FOR THIS REVIEWER TO FOLLOW THE | | | GREASE DUCT AND RELATED DUCTS FOR THIS HOOD SUBMITTAL. | | | FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | |
|