Plan Review Notes
Plan Review Notes For Permit 22051201
Permit Number 22051201
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-08 08:02:58PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN OF
 THIS PROJECT. FBC 107.2.1
 PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. IS THE MECHANICAL SYSTEM GOING TO BE
 CHANGED OUT? IF NOT IS THE EXISTING UNIT SIZED TO ADD
 THE NEW SQUARE FOOTAGE TO THE SYSTEM? FEC R403.7.1
 REVISE THE DRAWING TO SHOW THE DRYER DUCT AND EXHAUST
 TERMINATION LOCATION. FRC M1502
 PROVIDE MORE INFORMATION ABOUT THE KITCHEN HOOD. IS IT
 DUCTED TO THE OUTDOORS? IF SO SHOW THE TERMINATION
 LOCATION AND THE HOOD MOTOR CFM'S. FRC M1503
  
  
  