| 2022-10-03 06:50:49 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW APPROVED WIYH PROVISO: |
| | |
| | 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE |
| | ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN. |
| | 34" MAX.). |
| | 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION |
| | PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT |
| | LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA |
| | BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS |
| | MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING |
| | FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2 |
| | ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55 |
| | OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED |
| | STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER |
| | PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS). |
| | THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO |
| | 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1. |
| | APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD. |
| | PLEASE REVISE PLAN SHEET A???1 OCCUPANT LOADS |
| | (INCLUDING |
| | STANDING AREA BEHIND BAR), PLAN SHEET A???2 SHOWING A |
| | SEATING PLAN INDICATING UNCONCENTRATED TABLES AND |
| | CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS |
| | APPLICABLE. |
| | 3.) FBC B 107.2.1, ON PLAN SHEET A???2 DOOR |
| | SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS |
| | A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN |
| | THE PRODUCT APPROVAL. |
| | |
| | |