Plan Review Notes
Plan Review Notes For Permit 22051156
Permit Number 22051156
Review Stop M
Sequence Number 3
Notes
Date Text
2022-09-16 08:19:24PLEASE SEE BELOW, THE OUTDOOR AIR CALCULATIONS FOR THIS
 OCCUPANCY MUST BE CALCULATED BY USING FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
  
 OCCUPANCY CLASSIFICATION SQUARE
 FOOTAGE SQFT/1000 OCCUPANT DENSITY #/1000 FT2 (A) TOTAL
 OCCUPANTS PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING
 ZONE,RP?? CFM/PERSON OUTDOOR AIRFLOW RATE IN BREATHING
 ZONE, CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN
 BREATHING ZONE,RA?? CFM/FT2 (A) AREA OUTDOOR AIRFLOW
 RATE "TOTAL OUTDOOR AIR REQUIRED
 "
 BARS, COCKTAIL
 LOUNGES 144 0.144 100 15 7.5 112.5 0.18 25.92 138.42
 BARS, COCKTAIL
 LOUNGES 272 0.272 100 28 7.5 210 0.18 48.96 258.96
 KITCHENS (COOKING)
 (B) 92 0.092 20 2 7.5 15 0.12 11.04 26.04
 KITCHENS (COOKING)
 (B) 182 0.182 20 4 7.5 30 0.12 21.84 51.84
 MAIN ENTRY LOBBIES 245 0.245 10 3 5 15 0.06 14.7 29.7
 CORRIDORS 80 0.08 - 0 - 0 0.06 4.8 4.8
 TOTALS 1,015 510
  