| Plan Review Notes For Permit 22051156 |
| Permit Number |
22051156 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-16 08:19:24 | PLEASE SEE BELOW, THE OUTDOOR AIR CALCULATIONS FOR THIS | | | OCCUPANCY MUST BE CALCULATED BY USING FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | | | | OCCUPANCY CLASSIFICATION SQUARE | | | FOOTAGE SQFT/1000 OCCUPANT DENSITY #/1000 FT2 (A) TOTAL | | | OCCUPANTS PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING | | | ZONE,RP?? CFM/PERSON OUTDOOR AIRFLOW RATE IN BREATHING | | | ZONE, CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN | | | BREATHING ZONE,RA?? CFM/FT2 (A) AREA OUTDOOR AIRFLOW | | | RATE "TOTAL OUTDOOR AIR REQUIRED | | | " | | | BARS, COCKTAIL | | | LOUNGES 144 0.144 100 15 7.5 112.5 0.18 25.92 138.42 | | | BARS, COCKTAIL | | | LOUNGES 272 0.272 100 28 7.5 210 0.18 48.96 258.96 | | | KITCHENS (COOKING) | | | (B) 92 0.092 20 2 7.5 15 0.12 11.04 26.04 | | | KITCHENS (COOKING) | | | (B) 182 0.182 20 4 7.5 30 0.12 21.84 51.84 | | | MAIN ENTRY LOBBIES 245 0.245 10 3 5 15 0.06 14.7 29.7 | | | CORRIDORS 80 0.08 - 0 - 0 0.06 4.8 4.8 | | | TOTALS 1,015 510 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | | | | |
|