Plan Review Notes
Plan Review Notes For Permit 22051156
Permit Number 22051156
Review Stop B
Sequence Number 3
Notes
Date Text
2022-09-22 17:08:57PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISOS:
  
 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE
 ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN.
 34" MAX.).
 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION
 PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT
 LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA
 BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS
 MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING
 FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2
 ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55
 OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED
 STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER
 PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS).
 THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO
 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1.
 APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD.
 PLEASE REVISE PLAN SHEET A-1 OCCUPANT LOADS (INCLUDING
 STANDING AREA BEHIND BAR), PLAN SHEET A-2 SHOWING A
 SEATING PLAN INDICATING UNCONCENTRATED TABLES AND
 CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS
 APPLICABLE.
 3.) FBC B 107.2.1, ON PLAN SHEET A-2 DOOR
 SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS
 A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN
 THE PRODUCT APPROVAL.
  