| 2022-08-18 08:39:19 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. THE WATER DIAGRAM SHOULD REFLECT THE CHANGE. IT | | | MIGHT BE HELPFUL TO ALSO INCLUDE A DETAIL OF THE WATER | | | HEATER SO AS TO SHOW THE PROPER RETURN AND | | | CONFIGURATION OF THE CIRCULATION LOOP. YOU COULD ALSO | | | DETAIL THE CONNECTIONS AT THE LAVATORIES SHOWING THE | | | COMPLIANCE WITH ASSE 1070 -------------2017 WPB AMENDS | | | 107.3.5.1.3(3) - PLEASE SUPPLY A WATER PIPING DIAGRAM. | | | INCLUDE DETAILS OF HOT WATER PROTECTION AS WELL AS | | | TEMPERED WATER PROTECTION IN COMPLIANCE WITH FPC | | | 607.1.1 AND 607.1.2. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|