| Plan Review Notes For Permit 22051156 |
| Permit Number |
22051156 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-18 13:21:22 | FIRE REVIEW COMMENT: | | | | | | DOOR C, THE REAR PATIO DOOR, THE DOOR LEAF SWING IS | | | ENCROACHING INTO THE MEANS OF EGRESS WIDTH. | | | | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF | | | EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH | | | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING | | | UNOBSTRUCTED, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | | OF | | | EGRESS SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO | | | THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING, | | | UNLESS THE DOOR LEAF IS EQUIPPED WITH AN APPROVED | | | SELF-CLOSING | | | DEVICE AND IS NOT REQUIRED BY THE PROVISIONS OF | | | 7.2.1.4.2 | | | TO SWING IN THE DIRECTION OF EGRESS TRAVEL. | | | 7.2.1.4.3.3 SURFACE-MOUNTED LATCH RELEASE HARDWARE ON | | | THE | | | DOOR LEAF SHALL BE EXEMPT FROM BEING INCLUDED IN THE | | | MAXIMUM | | | 7 IN. (180 MM) PROJECTION REQUIREMENT OF 7.2.1.4.3.1, | | | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: | | | (1) THE HARDWARE IS MOUNTED TO THE SIDE OF THE DOOR | | | LEAF THAT | | | FACES THE AISLE, CORRIDOR, PASSAGEWAY, OR LANDING WHEN | | | THE | | | DOOR LEAF IS IN THE OPEN POSITION. | | | (2) THE HARDWARE IS MOUNTED NOT LESS THAN 34 IN. (865 | | | MM), | | | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|