Plan Review Notes For Permit 22051156
Permit Number 22051156
Review Stop M
Sequence Number 1
Notes
Date Text
2022-06-21 13:46:351ST REVIEW FMC
 PERMIT: 22051156
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IDENTIFY RTU?S ON THE DRAWING. FBC 107.2.1
  
 2) FRONT BATH EXHAUST FAN DOES NOT SHOW WHERE THE
 EXHAUST TERMINATION LOCATION WILL BE, REVISE PLAN TO
 SHOW THE TERMINATION LOCATION. FMC 501.3.1
  
 3) PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH USE OF
 SPACE IDENTIFIED WITH AN OCCUPANCY CLASSIFICATION FROM
 FMC TABLE 403.3.1.1; EXAMPLE- LOUNGE AREA AND TASTING
 ROOMS ARE NOT AN OCCUPANCY CLASSIFICATION FROM TABLE
 403.3.1.1
  
 4) REVISE PLAN TO SHOW THE REQUIRED EXHAUST FOR THE
 KITCHEN/FOOD PREP AREA. FMC TABLE 403.3.1.1
  
 5) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE NEW
 RTU AND ANY GUARDS THAT MAY BE REQUIRED. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  