| 2022-07-13 17:14:34 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL NUMBER |
| | AND PRODUCT APPROVAL COVER SHEET FOR STORE FRONT DOORS. |
| | ALSO, PROVIDE THE DESIGNER OF RECORD'S REVIEW STAMP |
| | APPROVAL ON PRODUCT APPROVAL. |
| | 2.) FBC B 1010.1.2.1, THE DOORS MUST SWING IN THE |
| | DIRECTION OF EGRESS INCLUDING WINE TASTING ROOMS AND |
| | LOUNGE AREA BACK DOOR. |
| | 3.) FBC B 1014.6, THE HANDRAIL DETAILS NEED TO SHOW THE |
| | 12" EXTENSIONS WHERE TERMINATING. |
| | 4.) FBC B 1607.8.1 & FBC B 1607.8.8.1, THE HANDRAIL |
| | DETAILS NEED TO INDICATE THAT THEY CAN RESIST LINEAR |
| | LOADS OF 50 POUNDS AND A CONCENTRATED LOAD OF 200 |
| | POUNDS. |
| | 5.) FBC B 1604.8.3 & FBC B 1607.4, THE DECK DETAILS |
| | NEED TO INDICATE THAT THE REQUIRED VERTICAL, LATERAL, & |
| | CONCENTRATED LIVE LOADS ARE BEING MET. SEE FBC B TABLE |
| | 1607.1 |
| | 6.) FBC A 902.3, THE DINING SURFACE/BAR MUST SHOW |
| | COMPLIANCE WITH THE ACCESSIBILITY CODE. |
| | 7.) FBC B 1012.6.4, THE RAMP LANDING AT THE CHANGE OF |
| | DIRECTION NEEDS TO INDICATE A MINIMUM SIZE OF 60" X |
| | 60". |
| | 8.) FBC B 2304.10, PROVIDE ON PLANS THE FASTENERS AND |
| | CONNECTORS THAT WILL BE USED FOR DECK CONSTRUCTION. |