| 2022-06-22 15:17:36 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22051104 |
| | 6/22/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GREASE INTERCEPTOR SHALL BE INSTALLED UNDER A |
| | SEPARATE PERMIT. PLEASE NOTE THE FOLLOWING: |
| | DUE TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR |
| | PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF |
| | THE PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION ?TBD? |
| | (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| | SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE |
| | THE REVIEW STATUS TO PASS. |
| | |
| | 1) SHEET P1.1: SHOW THE LOCATION OF THE FULL OPEN VALVE |
| | FOR THE WATER DISTRIBUTION LINE IN THE SPACE- SECTION |
| | 606.1 FBC P. |
| | |
| | 2) P1.1: SHOW THE LOCATIONS OF CLEANOUTS FOR THE |
| | BUILDING DRAIN AND GREASE WASTE LINE AS REQUIRED BY |
| | SECS. 708.1.1 & 708.1.1 FBC P. |
| | |
| | 3) P5.1: PROVIDE A MEANS OF LIMITING THE HOT WATER |
| | TEMPERATURE TO THE 3-COMPARTMENT SINK AND MOP SINK |
| | USING EITHER A MASTER THERMOSTATIC MIXING VALVE AT THE |
| | WATER HEATER, OR POINT OF USE MIXING VALVES AT THE |
| | FIXTURES- SEC. 607.1.1 FBC P. PLEASE NOTE THAT ASSE |
| | 1070 MIXING VALVES ARE FOR TEMPERED WATER DELIVERY- |
| | SEC. 607.1.2 FBC P. IF INSTALLING A MASTER THERMOSTATIC |
| | MIXING VALVE AT THE WATER HEATER, PLEASE REVIEW SEC. |
| | 607.2.2 FOR COMPLIANT PIPING CONNECTIONS. |
| | |
| | 4) P5.2: PLEASE CORRECT THE 3-COMPARTMENT SINK DRAIN |
| | DETAIL TO SHOW EACH WELL OF THE FIXTURE DISCHARGING |
| | INDIVIDUALLY INTO THE FLOOR SINK- SEC. 802.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |