Plan Review Notes
Plan Review Notes For Permit 22051104
Permit Number 22051104
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-27 13:25:05FIRE COMMENTS:
 NFPA 101 LIFE SAFETY CODE
 (1)
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY,
 A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION
 FROM THE
 EGRESS SIDE.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO
 HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED
 THAT ALL
 OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43
 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
 (2)
 9.9 PORTABLE FIRE EXTINGUISHERS
 PORTABLE FIRE EXTINGUISHERS SHALL BE SELECTED,
 INSTALLED, INSPECTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 10.
 ANY AND ALL WORK ON THE FIRE SPRINKLE AND/OR FIRE ALARM
 SYSTEMS SHALL BE PERFORMED UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS AND PERFORMED BY PROPERLY LICENSED
 CONTRACTORS.
  