| Plan Review Notes For Permit 22051093 |
| Permit Number |
22051093 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-29 09:09:28 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PROPOSED ELEVATION CERTIFICATE LINE B9 = ELEVATION | | | CERTIFICATE PROVIDED SHOWS THE BASE FLOOD ELEVATION AT | | | 8.00 THE BUILDINGS LOWEST FLOOR (LIVING SPACE) WILL | | | NEED TO BE 2 FEET ABOVE THE BASE FLOOD ELEVATION PER | | | CITY ORDINANCE. (PLEASE VERIFY THE BASE FLOOD | | | ELEVATION) | | | | | | 2) ELEVATION CERTIFICATE A9(B) SHOWS 3 FLOOD VENTS - | | | DRAWING SHOWS 4. (ELEVATION CERTIFICATE SHOULD MATCH | | | THE DRAWINGS) | | | | | | 3) ELEVATION CERTIFICATE A9(C) - FOR 650 SQUARE FEET OF | | | GARAGE SPACE - 650 SQUARE INCHES OF FLOOD VENTS ARE | | | REQUIRED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|