| 2022-07-25 09:42:21 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE REQUIRED FLOOD VENTS FOR THE GARAGE |
| | - FBC R322.2.2 |
| | |
| | 2) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - |
| | FBC WPB 107.3.5.3 |
| | |
| | 3) PLEASE SHOW THE DRAFT STOP WITHIN THE FLOOR TRUSSES |
| | - TYPE AND LOCATION - FBC R302.12 |
| | |
| | 4) PLEASE SHOW THE ROOF SLOPE DIMENSION AND MATERIAL |
| | USED FOR THE ROOF SLOPE - FBC R905.9.1 SLOPE. |
| | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS |
| | THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (2-PERCENT SLOPE) FOR DRAINAGE, |
| | |
| | 5) PRODUCT APPROVAL FOR THE FRENCH DOOR - FL22527 -10 - |
| | THE FRONT PAGE OF THE PRODUCT APPROVAL "STATUS" SHOWS |
| | "PENDING FBC APPROVAL" - THE STATUS MUST STATE |
| | "APPROVED". PLEASE PROVIDE A PRODUCT APPROVAL WITH AN |
| | APPROVED STATUS. |
| | |
| | 6) WINDOW AND DOOR SHOP DRAWINGS PROVIDED NEED TO BE |
| | SIGNED AND SEALED BY THE DESIGNER AND REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD - |
| | FBC WPB 107.3.4 |
| | |
| | 7) PRODUCT APPROVAL FOR THE FRONT DOOR (FL21891.13) IS |
| | MISSING THE FRONT PAGES OF THE PRODUCT APPROVAL - IT |
| | ALSO NEEDS TO BE REVIEWED AND MARKED APPROVED BY THE |
| | BUILDING DESIGNER OF RECORD - FBC WPB 107.3.4 |
| | |
| | 8) PLEASE SHOW GARAGE CEILING TO COMPLY WITH FBC R302.6 |
| | |
| | 9) PLEASE SHOW DOOR FROM GARAGE TO LIVING AREA TO |
| | COMPLY WITH FBC R302.5.1 |
| | |
| | 10 ) PLEASE SHOW ROOM UNDER STAIRWAY TO COMPLY WITH FBC |
| | R302.7 UNDER-STAIR PROTECTION. |
| | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR |
| | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE |
| | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH |
| | 1/2-INCH (12.7 MM) GYPSUM BOARD. |
| | |
| | 11) PLEASE SHOW CEILING HEIGHTS - FBC R305.1 |