Plan Review Notes
Plan Review Notes For Permit 22051093
Permit Number 22051093
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-25 09:42:21NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED FLOOD VENTS FOR THE GARAGE
 - FBC R322.2.2
  
 2) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC WPB 107.3.5.3
  
 3) PLEASE SHOW THE DRAFT STOP WITHIN THE FLOOR TRUSSES
 - TYPE AND LOCATION - FBC R302.12
  
 4) PLEASE SHOW THE ROOF SLOPE DIMENSION AND MATERIAL
 USED FOR THE ROOF SLOPE - FBC R905.9.1 SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS
 THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE,
  
 5) PRODUCT APPROVAL FOR THE FRENCH DOOR - FL22527 -10 -
 THE FRONT PAGE OF THE PRODUCT APPROVAL "STATUS" SHOWS
 "PENDING FBC APPROVAL" - THE STATUS MUST STATE
 "APPROVED". PLEASE PROVIDE A PRODUCT APPROVAL WITH AN
 APPROVED STATUS.
  
 6) WINDOW AND DOOR SHOP DRAWINGS PROVIDED NEED TO BE
 SIGNED AND SEALED BY THE DESIGNER AND REVIEWED AND
 MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD -
 FBC WPB 107.3.4
  
 7) PRODUCT APPROVAL FOR THE FRONT DOOR (FL21891.13) IS
 MISSING THE FRONT PAGES OF THE PRODUCT APPROVAL - IT
 ALSO NEEDS TO BE REVIEWED AND MARKED APPROVED BY THE
 BUILDING DESIGNER OF RECORD - FBC WPB 107.3.4
  
 8) PLEASE SHOW GARAGE CEILING TO COMPLY WITH FBC R302.6
  
 9) PLEASE SHOW DOOR FROM GARAGE TO LIVING AREA TO
 COMPLY WITH FBC R302.5.1
  
 10 ) PLEASE SHOW ROOM UNDER STAIRWAY TO COMPLY WITH FBC
 R302.7 UNDER-STAIR PROTECTION.
 ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR
 OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE
 AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH
 1/2-INCH (12.7 MM) GYPSUM BOARD.
  
 11) PLEASE SHOW CEILING HEIGHTS - FBC R305.1